4.3.1.1 GlobalBusStateField for PROFIBUS

FP7 Fieldbus Master Units Technical Manual
PROFIBUS (see p. 27)
DeviceNet (see p. 30)
CANopen (see p. 35)
PROFINET IO (see p. 37)
Identifier part Identifier
Global bits
GlobBit_Status
Status
GlobBit_Status
Error remote
ErrRe-
address
mAddr_ErrEvent
Error event
ErrRe-
mAddr_ErrEvent
Bus error
BusErrorCnt
count
Timeout
TimeOutCount
count
Explanation
Lower byte of the WORD. Details follow the
table.
Higher byte of the WORD.
The master system can be in one of the fol-
lowing states:
16#00: OFFLINE
16#40: STOP
16#80: CLEAR
16#C0: OPERATE
Lower byte of the WORD.
Some of the global bits indicate errors in the
network or in the FMU itself that require a
more detailed explanation. In these cases,
"ErrRemAddr" represents the source of the
error and can arise from either the FMU itself
(value = 255), or be detected and reported by
a network device. In this case, the lower byte
represents the station address. Range: 0 to
125.
Higher byte of the WORD.
Each error is assigned a number. The errors
are explained following the table.
Counts severe bus errors, e.g. bus short cir-
cuits.
Counts the number of rejected PROFIBUS tele-
grams due to severe bus errors.
Programming information
27