EXCEL 50 - USER GUIDE
Confirm with ENTER.
If 'Contr. Setup.' has been selected, the following screen will appear:
HW-Interf. Cfg.
›B-Port
C-Bus
LON-Bus
The contents of this list box will depend upon the controller's exact hardware con-
figuration. The listed interfaces to be configured will be from among the following:
 B-Port
 C-Bus.
 LON-Bus
 Modem
B-Port
Using the arrow keys, move the cursor to 'B-Port' and confirm with ENTER. The
following screen appears:
B-Port Config.
Baudrate: ›9600
Using the arrow keys, move the cursor to the value field. Use the '+' and '–' keys to
change the field. Confirm with ENTER.
NOTE: Live CARE is now capable of autodetecting the controller baud rate setting,
then of switching it temporarily to 38.4 Kbaud. When Live CARE is
disconnected, the controller will switch back to the previous baud rate
setting automatically within 15 seconds.
Using the arrow keys, move the cursor to 'BACK'. Confirm with ENTER.
C-Bus
Using the arrow keys, move the cursor to the 'C-Bus' field and confirm with ENTER.
The following screen appears:
C-Bus Config.
Baudrate: ›38400
Contr.No: ›<no.>
NOTE: If you set the bus ID to a non-zero value, the C-bus baudrate will be
immediately disabled (i.e. it is then no longer editable). See also
section "L
Using the arrow keys, move to the appropriate value field.
If 'Baudrate' is selected:
Change the baud rate using the '+' and '–' keys. Confirm with ENTER.
If 'Contr. No.' is selected:
Change the controller number using the '+' or '–' keys. Confirm with ENTER.
IMPORTANT
If no controller number is set or if the number shown is not reconfirmed, the
controller will not go online on the C-Bus after start-up.
Using the arrow keys, move the cursor to 'BACK'. Confirm with ENTER.
1
›BACK
›BACK
W
Bus" below.
ON
ORKS
49

Controller Setup

EN2B-0137GE51 R0216