EXCEL 50 - USER GUIDE
Digital Points
Remote Points
Analog Outputs
Using the arrow keys, move the cursor to 'NEXT'. Confirm with ENTER. Except in
the case of Remote Analog points, the following screen appears:
<
>
user addr.
Input: <
NV index
<
>
nvi name
›BACK
›NEXT
This screen shows the mapping of data points to network variables transmitted on
the L
W
bus. If no network variables have been mapped, the index and NV
ON
ORKS
name fields will be blank. This screen appears also for outputs, with NV index for the
output and nvo name displayed.
In the case of Remote Analog points only, the following screen appears:
Trend hysteresis
1.0 Pct
Trend Cycle:
›BACK
0000 min
To change the attributes "Trend Hysteresis" or "Trend Cycle", use the arrow keys to
move the cursor to the appropriate field. Confirm with ENTER.
Change the value/status using the '+' or '–' keys.
NOTE: If "Trend Cycle" is set to anything other than 0000, time-based trending is
enabled. If "Trend Cycle" is set to 0000, then value-hysteresis trending is
enabled using the percent value show for "Trend Hysteresis".
This screen is visible only for digital points and shows the relationship between the
physical state of a digital point and its logical status.
<
>
user addr.
Normally Closed
›YES
›BACK
›NEXT
The attribute "Normally Open/Normally Closed" of the user address can be changed
from 'YES' to 'NO' and vice versa. Using the arrow keys, move the cursor to the
appropriate field. Confirm with ENTER.
Using the arrow keys, move the cursor to 'NEXT'. Confirm with ENTER.
This screen is visible only for remote points and shows the controller number of a
remote point.
<user addr.>
RemoteController
Number:
›BACK
›NEXT
Change the controller number using the '+' and '–' keys. Confirm with ENTER. In the
case of points which the controller receives from other controllers on the C-Bus, the
controller number of the source of the point must be entered. For points that the
controller is the source of, the default value of 0 is required.
Using the arrow keys, move the cursor to 'NEXT'. Confirm with ENTER.
This screen is visible only for analog outputs and shows - for example - the time an
actuator needs to open and close a valve.
31
>
0
EN2B-0137GE51 R0216