EN2B-0137GE51 R0216
This is the first screen of the start-up sequence. It shows the version of the company
name, the controller name, and the firmware version. The cursor is positioned at
'NEXT' by default. Confirm with ENTER.
Date: ›16.08.2010
Time: ›14:29
Ctr. No: ›4
›NEXT
Using the arrow keys, move the cursor to
— the 'Date' field to enter the current date.
— the 'Time' field to enter the current time.
— the 'Ctr. No' field to set the controller number.
If 'Date' is selected:
Set the date using the '+' or '–' keys. Use the arrow keys to move from field to field.
Confirm with ENTER. Using the arrow keys, move the cursor to 'BACK'. Confirm with
ENTER to return to the previous screen.
NOTE: The date must be entered in the following format: DD. MM. YYYY; for
example, 23. July 2009 must be entered as 23. 07. 2009. Press the
CANCEL key to abort the operation or to cancel an incorrect entry before
ENTER has been pressed. The value previously displayed will be restored.
If 'Time' is selected:
Set the time using the '+' or '–' keys. Use the arrow keys to move from field to field.
Confirm with ENTER. Use the CANCEL key to return to the previous screen.
NOTE: The time must be entered in the following format: HH:MM in 24-hour clock
format; for example: 9:30 a.m. must be 09:30 and 9:30 p.m. must be
21:30. Press the CANCEL key to abort the operation or to cancel an
incorrect entry before ENTER has been pressed. The value previously
displayed will be restored.
If 'Ctr. No.' is selected:
Set the controller number using the '+' or '–' keys. Confirm with ENTER.
IMPORTANT
If no controller number is set or if the number shown is not reconfirmed, the
controller will not go online on the C-Bus after start-up.
Using the arrow keys, move the cursor to 'NEXT'. Confirm with ENTER.
Modem Part:
<
active/inactive
Appl. Mem. Size
›NEXT
128 KB
This screen provides information about whether modem communication is enabled
and about application memory size. Enabling modem communication and changing
the value for application memory are done in a later screen. The cursor is positioned
at 'NEXT' by default. Confirm with ENTER.
›Contr. Setup
›Select Applic.
›Requ. Download
›DP Wiring Check
Using the arrow keys, move the cursor to
— 'Contr. Setup' to configure the controller-specific hardware interfaces.
— 'Select Applic.' to choose the application manually.
— 'Requ. Download' to download an application from either the PC-based XL-
Online operator and service software or the XBS Central A.
— 'DP Wiring Check' to set up the test mode with default user addresses.
48
EXCEL 50 - USER GUIDE
>