WARNING: Qualified Service Personnel ONLY must perform the Installa- To ensure reliable operation of the UPS and to protect the UPS from over- tion and Servicing of these UPS systems. MINUTEMAN accepts no liabilities heating, these vents and openings must not be blocked or covered. Do not and is not limited to: injury to the User or Service Personnel, or damages to;...
Page 4
CAUTION! Receiving Inspection To de-energize the outputs of the UPS: After removing your UPS from its carton, it should be inspected for damage 1. If the UPS is on press and then release the OFF button after the audible that may have occurred in shipping. Immediately notify the carrier and place alarm beeps twice to turn the UPS off.
Chapter 2: Controls and Indicators 1. Displays the power flow of the UPS: AC Mode Power Flow Bypass Mode Power Flow Battery Mode Power Flow 1. The ON button is to turn the UPS on. Pressing the ON button during the 2.
REAR PANEL Input Power Plug Model # Output Power Receptacles (All power cords are 6ft) NEMA 5-15P EC1000LCD 6-NEMA 5-15R (Controllable) EC1500LCD NEMA 5-15P 6-NEMA 5-15R (Controllable) EC2000LCD NEMA 5-20P 8-NEMA 5-15/20R (Controllable) 8-NEMA 5-15/20R (Controllable) EC3000LCD NEMA L5-30P 1-NEMA L5-30R (Always On) Chapter 3: Installation INSTALLATION PLACEMENT This UPS series is ONLY intended to be installed in an indoor temperature controlled...
Page 7
FIG. 3 FIG. 4 CONNECTING THE BATTERIES (QUALIFIED SERVICE PERSONNEL ONLY) Please read all of the WARNINGS and CAUTIONS before attempting to con- nect the batteries. WARNING: Use two or more people when installing the UPS, the UPS is extremely heavy. 1.
The UPS will charge the batteries when the UPS is in the on or off position as COMMUNICATIONS PORT CONNECTION (OPTIONAL) The Power Monitoring Software and interface cables can be used with the UPS. long as the UPS is plugged into the wall outlet and there is an acceptable AC Use only the interface cables that come with these UPSs.
Page 9
The output receptacles are electrically wired into two segments to support the "Load of the Minuteman SentryHD software. See the software CD for the installation of Shedding Function" (Labeled 1 & 2). The user can control the two segments indi- the Power Monitoring Software.
Page 10
ALARMS Chapter 5: Configurable Parameters and Settings ON BATTERY When the UPS is operating on the batteries, the On-Battery icon will illumi- (These items may require optional software or hardware) nate, the Utility power LED (Green) will extinguish and the audible alarm will sound one beep every ten-seconds.
Para Systems Inc. Er38: Failed to synchronize Turn the UPS off, unplug the power cord, wait for 5-minutes and MINUTEMAN UPS with utility input. then restart the UPS. If the error did not clear call for service. 1809 W. Frankford Road, Suite 150 Carrollton, TX 75007 Er39: Low Battery Capacity.
Chapter 8: Replacing the Battery BATTERY REPLACEMENT PROCEDURE QUALIFIED SERVICE PERSONNEL ONLY QUALIFIED SERVICE PERSONNEL ONLY Please read all of the WARNINGS and CAUTIONS before attempting to ser- PLEASE READ ALL OF THE CAUTIONS AND THE WARNINGS BEFORE vice the batteries. Typical battery life is 3 to 5 years. Environmental factors ATTEMPTING TO REPLACE THE BATTERY MODULE do affect battery life.
Page 13
7. Press the spring loaded latch on the battery retaining bracket at the bottom, FIG. 3 pull it outward and then set it aside (FIG. 2) 8. Press down to unlock the battery connector holders (FIG. 3). 9. Disconnect the battery connectors (FIG. 3) 10.Grasp the battery pull tab and gently pull the battery module out of the UPS and set it aside.
Chapter 9: Specifications BATTERY SYSTEM Battery Type Sealed, Non-Spillable, Maintenance Free, Value Regulated Lead Acid SYSTEM SPECIFICATIONS Typical Recharge Time 8-hours to 90% after full load discharge Typical Battery Life 3-5 years, depending on discharge cycles and ambient temp EC1000LCD EC1500LCD EC2000LCD EC3000LCD...
Para Systems. For equipment located outside of the United States and Canada, Para Systems only covers faulty parts. Para Systems Manufacturer’s Name: Para Systems, Inc. (MINUTEMAN UPS) products that are depot repaired or replaced pursuant to this warranty shall only be warranted for the unexpired portion of the warranty applying to the original product.