Horizontal Side Termination; Horizontal Side Or Rear Snorkel Termination; Corner Location, Horizontal Termination, 45° Pipe Bend - Valor 535 XAN Installation And Owner's Manual

Direct vent gas fireplace heater
Table of Contents

Advertisement

4.3. Horizontal side termination

See figures 5 &6.
Can be used with either #551DVK standard vent kit
or another terminal cap and accessories.
Adapter #817VAK, one 90° vent elbow and pipe
lengths will be required.
(See venting options section of this manual).
All vent length dimensions and clearance limits are
as section 4.2.
The minimum floor location is shown in figure 6.
4.4. Horizontal side or rear
snorkel termination
The dimensional requirements in sections
4.2 and 4.3 apply.
Adapter #817VAK, one 90° vent elbow and
pipe lengths will be required.
A thimble kit may also be necessary.
(See venting section of this manual).
4.5. Corner location, horizontal
termination, 45° pipe bend
See figures 5 & 7.
Can be used with either #551DVK standard
vent kit or another terminal cap and
accessories.
Adapter #817VAK, one 90° vent elbow and
pipe lengths will be required. (See venting
section of this manual).
All vent length dimensions and clearance
limits are as section 4.2.
The minimum corner location is shown in fig. 7.
Figure 6
Figure 7
11