Trade-wind PMB02 Installation Instructions & Use & Care Manual

Trade-wind PMB02 Installation Instructions & Use & Care Manual

Pmb series

Advertisement

PMB Series Models
Width
Model
&
Depth
PMB02
22" x 12"
PMB03 *
22" x 12"
PMB06
22" x 12"
* 390CFM Code Compliant
Before beginning installation, please thoroughly read and become familiar with these instructions. Installation and
service must be completed by a qualified installer. Failure to properly install this product may void the warranty.
Installer:
Please leave Installation Instructions with the range hood liner.
Owner:
Please keep Installation Instructions for local electrical inspector's use and for future reference.
WARNINGS: Must be followed carefully to avoid personal injury.
IMPORTANT: Must be followed carefully to avoid damage or incorrect installation.
TIPS: Contain helpful information to facilitate installation.
WARNING! TO REDUCE THE RISK OF FIRE, ELECTRICAL SHOCK, OR INJURY TO
PERSONS OBSERVE THE FOLLOWING:
a) Use this unit only in the manner intended by the manufacturer. If you have any questions, please contact the
manufacturer at the address or telephone number listed in the warranty.
b) Before servicing or cleaning unit, switch power off at service panel and lock service panel and lock the service
disconnection means to prevent power from being switch on accidentally. When the service disconnecting means
cannot be locked, securely fasten a prominent warning device, such as a tag to the service panel.
CAUTION
-- For general ventilating use only. Do not use to exhaust hazardous or explosive materials
and vapors.
WARNING – TO REDUCE THE RISK OF A RANGE TOP GREASE FIRE:
a) Never leave surface units unattended at high settings. Boilovers cause smoking and greasy spillovers that may
ignite. Heat oils slowly on low or medium settings.

Installation Instructions

Type of
CFM
Motor &
Blower
240
Internal
390
Internal
600
Internal
READ AND SAVE THESE INSTRUCTIONS
Revised 10/13/2015
INSTALLATION INSTRUCTIONS &
USE & CARE GUIDE
PMB Series Models
Copyright (C) 2008
PMB06
Proverbs 22:29
Page 1
1

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the PMB02 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Trade-wind PMB02

  • Page 1: Installation Instructions

    USE & CARE GUIDE PMB Series Models PMB Series Models Width Type of Model & Motor & Depth Blower PMB02 22” x 12” Internal PMB03 * 22” x 12” Internal PMB06 22” x 12” Internal PMB06 * 390CFM Code Compliant Before beginning installation, please thoroughly read and become familiar with these instructions.
  • Page 2 b) Always turn hood ON when cooking at high heat or when flambéing food (i.e. Crepes Suzette, Cherries Jubilee, Peppercorn Beef Flambe’). c) Clean ventilating fans frequently. Grease should not be allowed to accumulate on fan or filter. d) Use proper pan size. Always use cookware appropriate for the size of the surface element. WARNING! TO REDUCE THE RISK OF INJURY TO PERSONS IN THE EVENT OF A RANGE TOP GREASE FIRE, OBSERVE THE FOLLOWING: a) SMOTHER FLAMES with a close-fitting lid, cookie sheet, or metal tray, then turn off the burner.
  • Page 3: Planning The Installation

    (minimum is 24”). This would typically result in the bottom of the hood being 66 - 72 inches (167.6 - 182.9 cm) above the floor. These dimensions provide for safe and efficient operation of the hood. Always observe local building codes. PMB02 PMB03 PMB06...
  • Page 4 THROUGH FILTER BRACKETS, ELECTRICAL COMPONENTS OR UL LABEL. ® Because the Trade-Wind Standard Series Liner was designed for various wood hood applications, no mounting holes have been pre-drilled. This allows the liner to be attached in most any area of the canopy that has a wood frame support, e.g., the back, sides or top.
  • Page 5: Electrical Connection

    OPERATING CONTROLS: Always activate the ventilator when using cooking appliances. For best performance, turn on the blower a few minutes before starting to cook to establish an airflow pattern within the room. To use the electronic touch control, touch the button that corresponds to the desired speed. To turn off blower, touch the illuminated speed button again or the illuminated blower off control button.
  • Page 6: Wiring Diagram

    INSTRUCTIONS: A 15 to 20 amp electrical service is recommended for proper electrical supply. Before determining, calculate amp ratings based on the product label found on the PMB series module. Always observe local building codes. Always use a dedicated circuit. Line load is calculated by adding the amperage of the halogen lights to the rated amperage of the ventilator..
  • Page 7: Warranty

    This warranty may be voided if any unauthorized service, alterations, or repairs are made to the product. What is Not Covered Normal maintenance and service of any product that has been subject to misuse, negligence, • ® accident, or installation inconsistent with the recommended Trade-Wind Installation Instructions ® and Trade-Wind Best Practices Guidelines.
  • Page 8: Best Practices

    Brands Best Practices Venting Installation Instructions for Range Hoods and Wood Hood Liners (All Models) —Addendum to Installation Instructions— IMPORTANT: Problems caused by improper installations are not covered by the manufacturer’s warranty. IMPORTANT: Undersized and improperly installed duct pipe and/or other ventilation components will cause excessive static pressure (air resistance), that may result in rattling, vibration and air buffeting noises, as well as inadequate ventilation. 1. Building Codes - Kitchen Hood Ventilators should be installed by qualified technicians familiar with state and local building codes. 2. Duct Pipe and Fittings (Elbows, Transitions, Roof & Wall Caps) a. Use round or rectangular rigid metal duct only. Where possible, use round duct as it creates the least amount of static pressure. DO NOT use flex duct. b. All duct sections and fittings (EXCEPT DAMPERS, per Section 4), should overlap and be connected with at least 3 – 4 equally spaced screws and wrapped tightly with 2 – 3 layers of Aluminum Foil Metal Duct Tape. This type of duct tape is more durable than traditional cloth duct tape. DO NOT use butt joints. c. For best air flow, elbows and pipe size transition fittings should not be directly connected to one another. Where possible, always include at least 15 inches of straight pipe between fittings. 3. Duct Pipe and Fitting Sizes. (See Duct Sizing Chart and Area Calculations Section for more detail) IMPORTANT: DO NOT use either of the following duct pipe sizes or fitting sizes for any kitchen hood ventilator installations: - 6” round duct pipe - 3.25” x 10” rectangular x 6” round transitions - 6” x 7” linear transitions IMPORTANT: No portion of any length of duct pipe or fitting should be smaller than the discharge port of the ventilator. This is very important because any type of restriction anywhere in the ventilation system will cause increased static pressure (air resistance), that may result in rattling, vibration and air buffeting noises, as well as inadequate ventilation. Example: For ventilator models with 3.25” x 10” discharge ports, no part of the roof cap or wall cap’s air path should be smaller than 3.25” x 10” (32.5 square inches) or 7” round (38.5 square inches). See Roof Caps and Wall Caps section for more detail.
  • Page 9 Duct Pipe and Fitting Sizes (Continued) Duct Runs – Length a. Configure the ventilation duct run to be as short and as direct to the outside as possible. Minimize the number of elbows and transition fittings used. Complex or long runs should be reviewed by a qualified installer. b. No portion of the ducting should be run so that the exhaust air flows downward. Since exhaust heat rises, forcing the air to flow downward will cause increased static pressure. As previously mentioned, improperly installed duct pipe will cause excessive static pressure (air resistance), that may result in rattling, vibration and air buffeting noises, as well as inadequate ventilation. c. Duct runs for 390CFM ventilator models should not exceed 20 linear feet with two 90-degree elbows (or four 45-degree elbows), a damper and a roof or wall cap. Longer runs or additional elbows will result in decreased ventilation performance. Each 90-degree elbow is the equivalent of 8 linear feet of duct pipe; each 45-degree elbow is equivalent to 4 linear feet of duct pipe. d. Always run ventilator ducts to the outdoors. DO NOT terminate a duct into an attic, basement, garage, crawl space under a house, a chimney, other ducting or an enclosed room. 4. Dampers IMPORTANT: DO NOT USE SCREWS TO ATTACH ANY TYPE OF DAMPER AS THE SCREWS MAY BLOCK THE DAMPER BLADES. IMPORTANT: DO NOT USE MORE THAN ONE DAMPER IN THE VENTILATION SYSTEM. NOTE: Many styles of roof caps and wall caps have built-in dampers. See Roof Caps and Wall Caps section for more detail. Always use carefully crafted, tightly wrapped Aluminum Foil Metal Duct Tape on all connections and physically view and test the damper blades to make certain they are opening and closing correctly. Make sure that the damper blades do not touch the duct walls and that there is no debris blocking the free movement of the damper mechanism. Common things to look for include screws protruding into the blade’s path, overspray of paint, plaster and insulation. If using rectangular duct, be sure that all four sides of the duct are on the outside of the damper’s start collar or frame. 390CFM Models 390CFM models have a 7" round Ducting and Damper. DO NOT USE SCREWS TO ATTACH THE DUCT TO THE DAMPER FRAME AS THE SCREWS MAY BLOCK THE DAMPER BLADE. ALWAYS use Aluminum Foil Metal Duct Tape on all connections and physically view the damper blade to make certain it is operating correctly. On ventilator installations designed to recirculate the exhaust air back into the kitchen, be sure to remove the aluminum damper blade before attaching the duct to the damper frame. Damper in Roof Cap or Wall Cap In ventilation systems utilizing a roof cap or wall cap with a built-in damper, do not install an additional in-line damper. Two dampers are unnecessary and will cause increased static pressure (air resistance), that may result in rattling, vibration and air buffeting noises, as well as inadequate ventilation.
  • Page 10 In-line dampers must be installed so that the exhaust air flow will open the butterfly blades. For horizontal duct runs, the in-line damper must be installed so that the hinge between the two butterfly blades is vertical—the hinge pin must point up and down. Otherwise, because of gravity, the damper’s blades will not close and the damper will not prevent backdrafts. For vertical duct runs, the in-line damper’s hinge will be horizontal (sideways), which is correct for vertical duct runs. Gravity will help close the damper blades after each use. For upward slanted duct runs, the in-line damper’s hinge must point to the top and bottom sides of the duct. In his position, gravity will help close the damper blades after each use. Otherwise, because of gravity, the damper’s blades will not close and the damper will not prevent backdrafts. 5. Roof Caps and Wall Caps The roof cap or wall cap is the termination point of the venting system that allows the exhaust air to exit to the outdoors. All sections of this fitting must have an equal or greater air path area than the ventilator’s discharge port. If any section of the roof cap or wall cap is smaller than the ventilator’s discharge port, the entire ventilation system will lose efficiency and the restriction will cause increased static pressure. IMPORTANT: Even though the intake side of the roof cap or wall cap may be properly sized, roof caps or wall caps with built-in dampers must be made so that when the damper is fully open, the actual open area of the final air path is equal to or greater than the discharge port of the ventilator. Any undersized portion of a roof cap or wall cap will cause excessive static pressure that may result in rattling, vibration and air buffeting noises, as well as inadequate ventilation. Roof caps and wall caps must have an integral bird screen. 6. Attaching Duct to House Framework The ventilation system should be attached to the framework in such a manner that the weight of the duct and fittings is supported with no stress on the duct joints, fittings or on the ventilator. All ducting should be attached so as to avoid any possible duct vibration from being transferred to the house’s framework. 7. Hoods with Optional Top or Back Venting Several range hood models provide the option of venting the exhaust air out the top or back side of the range hood. On some models, this is accomplished by redirecting the motor/blower unit to exhaust through the top, back or the recirculation position. On other models, the duct pipe is attached directly to the start collar which can be attached to the top side or back side of the hood. For more details on this aspect of the installation, see the detailed Installation Instructions packaged with each unit. IMPORTANT: On models with multiple venting ports, the open holes/slots around the unused venting port(s) MUST BE SEALED with Aluminum Foil Metal Duct Tape. Otherwise, exhaust air and smoke will be vented through the unused Vent Knockout’s holes/slots. On models featuring the recirculation option, if this option is NOT used, the vent port inside the hood should also be taped over with Aluminum Foil Metal Duct Tape. UNUSED PORTS SHOULD BE TAPED BEFORE THE RANGE HOOD IS MOUNTED TO THE WALL OR CABINET. 8. Liners Using Optional Vent Transition Accessory On installations using the optional vent transition accessory to transition to 10” round duct, all bottom edges of the transition should be taped to the liner with 2 – 3 layers of Aluminum Foil Metal Duct Tape.
  • Page 11 9. Duct Sizing Chart and Area Calculations Minimum Discharge Size Ventilator Discharge Port Duct Size Duct Type Required of Roofcap or Wallcap Types & Sizes (in Square Inches) Outside Opening 6” Diameter, Round 28.3” 6” Round Metal Duct 28.3” 28.3” 7” Diameter, Round 38.5” 7” Round Metal Duct 38.5” 38.5” 8” Diameter, Round 50.25” 8” Round Metal Duct or 50.25” 50.25” 6” x 9” Rectangular Metal Duct 54” 54” 10” Diameter, Round 78.5” 10” Round Metal Duct 78.5” 78.5” 3.25” x 10” Rectangular 32.5” 3.25” x 10” Rectangular Metal Duct 32.5” 32.5” Calculating Square Inches of Various Duct Sizes & Types ROUND DUCT RECTANGULAR DUCT Radius x Radius x 3.1416 = Area (Sq. Inches) Width...

This manual is also suitable for:

Pmb03Pmb06

Table of Contents