Download Print this page

Toshiba RAV-104 Series Installation Instructions Manual page 29

Advertisement

Available languages
  • EN

Available languages

  • ENGLISH, page 1
Heronhill - for all your Toshiba requirements
Precautions
This guide should be read and utilised in conjunction with the official published regulations and
!
codes of practice, be they local, national or international.
Each air conditioning system will have its own discrete power supply, with overload current
!
protection.
!
Install a multi-pole isolation switch (with 3mm separation) in the power supply circuit.
The current protective device will prevent and protect the supply cable against overcurrent.
!
The circuit protection must be selected having due regard to the compressor starting current, such
!
that the supply cables when sized correctly, are also protected.
The cable should be selected to match the nominal load of the system, in addition to the losses
!
associated with corrections for length, temperature, impedance, etc. In accordance with local
codes of practice.
Earth both the indoor and the outdoor units by attaching an Earth wire. Ensure this is carried out
!
according to National Wiring Regulations.
!
After having made the connection to the terminal board, secure the cables with a cable clamp.
!
Wiring for the power supply must be performed by a qualified electrical engineer or technician
only.
!
Do not allow the cables (used for the power supply and for wiring between the units) to come into
contact with valves or pipes not covered with insulators. Secure these cables to the parts of the
pipes with heat insulation fitted.
!
Use the Ø20mm knockouts provided on the units (except KH/KHR/K), to fit cable glands to hold
the cables securely at the point where they enter the electrical box or unit.
Power Supply Specifications
Model (RAV–)
Power Supply
Starting current (A)
Running current (A)
Power Supply Wiring
For a 3-phase model (4 wires), connect the power wiring to the L
!
power supply terminal block of the outdoor unit. For a single phase model, connect the power
wiring to the L and N terminals ( see drawing below ):
Models RAV-264AH8/A8, RAV-364AH8/A8, RAV-464AH8/A8 are equipped with a reverse phase
!
protector. If the compressor does not start, interchange phase L
Tel: 01823 665660
E
LECTRICAL
Main Circuit
134AH/A
164AH/A
220/240V – 1PH – 50Hz
60
60
10.7
11.1
380/415V 50Hz
3 phase 4 wires
~ 29 ~
~ 29 ~
www.heronhill.co.uk
W
IRING
264AH/A
264AH8/A8 364AH8/A8 464AH8/A8
380/415V – 3PH – 50Hz
80
25
14.8
4.7
, L
, L
and N terminals on the
1
2
3
220/240V 50Hz
Single phase
with phase L
2
Fax: 01823 665807
42
50
6.8
8.5
of the power supply.
3
GB

Advertisement

loading