Configuring The Alarm Ports - Nortel 1000M Installation And Commissioning Manual

Nortel networks communication server large system installation and commissioning
Hide thumbs Also See for 1000M:
Table of Contents

Advertisement

Page 168 of 456
Cabling the Candeo
Table 17
Alarm configuration – NT8D46xx
Label
Colour
DCON0
Black
DCON1*
Red
DCON2*
White
DDON3*
Green
ALARM
Orange
* Twist red, white and green together and connect to port 2 as Major
Jumper together and connect to battery return bus. J8-2,5,8

Configuring the alarm ports

NN43021-310
Standard 02.01
Configuring the system monitor
Table 16
Cable lengths
Cable
NT8D46AV
NT8D46BV
NT8D46CV
There are eight configurable Candeo output ports for output alarms. Each
output port can use one of the following three contact types: normally open,
normally closed, and common. Large Systems use normally closed contacts.
Common contacts connect to the Candeo battery return bus. The connector
strip J8 is used for all output connections and is removable from the System
Manager for ease of wiring. Ensure that pin 1 is in the correct orientation for
wiring when strip has been removed.
Candeo
alarm port
Port 1
Port 2
Port 2
Port 2
Port 3
Follow the steps in Procedure 17 to configure the alarm ports.
December 2007
Candeo
J8 connector
J8-1 Normally Closed
J8-1 Normally closed
J8-4 Normally closed
J8-4 Normally closed
J8-7 Normally Closed
Length
9.75 m (32 ft)
19.5 m (64 ft)
30 m (100 ft)
Candeo
configuration
Loss of AC power
Major alarms
Major alarms
Major alarms
Low float