Residential Installation; Clearances; Chimney And Connector; Double-Wall Connector - Pacific energy NEO 1.6 NEWCASTLE Installation And Operating Instruction

Table of Contents

Advertisement

Residential Installation

Warning: Under no circumstances is this woodstove to be
installed in a makeshift or "temporary" manner. It may be fired
only after the following conditions have been met.
*
DO NOT ATTEMPT TO CONNECT THIS WOODSTOVE
TO ANY AIR DISTRIBUTION DUCT.
*
Outside combustion air or fresh air into the room may be
required in your area, consult local building codes (see
Combustion Air section).
- The services of a competent or certified installer, (certified
by the Wood Energy Technical Training program (WETT) - in
Canada,or the Hearth Education Foundation (HEARTH) - in
U.S.A.,) are strongly recommended.
BOTH CHIMNEY SYSTEM AND CONNECTOR MUST BE
6"(150mm) DIAMETER AND LISTED TO:
* IN CANADA - ULC S-641 LISTED CONNECTOR AND
ULC-S-629 LISTED CHIMNEY,
* IN USA - UL-103 HT LISTED CONNECTOR AND CHIMNEY

Clearances

1. This woodstove may be installed using a single-wall con-
nector (smoke pipe) or listed double-wall connector (see
Mobile Home installation).
2. Clearances to combustible surfaces and materials using
single-wall connector are shown in Figure #10, page 13.
Clearances may be reduced with various heat insulating
materials. Consult local fire codes and authorities for ap-
proval.
3. Alternately, for close clearances, use a listed double-wall
connector. See Fig #10, page 13
It is possible to store wood between the stove supports, un-
derneath the unit but not recommended. The wood must not
extend further forward than flush with the supports.
NOTE: Refer to local fire codes, CAN-B365 in Canada and
NFPA 211 in the U.S..

Chimney and Connector

Connect to a listed chimney or a chimney suitable for use
with solid fuel that is lined and in good condition and meets
local building codes. The chimney flue size should be the
same as the stove outlet for optimal performance. Reduc-
ing or increasing the flue size may adversely affect stove
performance. Chimney flue exit is to be 3 feet (1 m.) above
roof and two feet (0.6 m.) above highest projection within 10
feet (3 m.). The installation must meet all local codes. Do not
connect this unit to a chimney flue serving another appliance.
Minimum system height is 15 feet (4.6 m.) (measured from
base of appliance).
12
©PACIFIC ENERGY FIREPLACE
PRODUCTS LTD.
*
The chimney connector shall not pass through an attic, roof
space, closet or similar concealed space, floor, or ceiling.
Where passage through a wall, or partition of combustible
material is desired, the installation shall conform to CAN/
CSA-B365, Installation Code for Solid-Fuel-Burning Appli-
ances and Equipment in Canada or, NFPA 211: Standard
for Chimneys, Fireplaces, Vents, and Solid Fuel-Burning
Appliances in the U.S..

Double-Wall Connector

-
Use a listed double-wall connector.
-
Install all components to the chimney connector manu-
facturer's installation requirements.

Single-Wall Connector

Smoke pipe must be:
*
as short and straight as possible, use six inch
diameter, 24 gauge black pipe that is clean and in new
condition.
*
secured at every joint and collar with 3 sheet metal screws.
*
installed with the crimped or male ends pointing down.
This will carry any liquid creosote or condensation back
into the stove.

Procedure

1. If a listed chimney and double-wall connector is to be
connected to the stove, install all components to the chim-
ney manufacturer's installation requirements. (Outside
combustion air may be required, consult local building
codes. See Combustion Air section on page 11.)
2. If it is desirable to use smoke pipe in conjunction with the
insulated chimney, see step 4.
3. If a roof or ceiling support is used in the installation, you
will find the chimney manufacturer's complete instructions
packed with the roof support.
4. To start installing smoke pipe (chimney connector), slip
crimped edge of the pipe inside the stove collar. Use
holes provided in collar to secure pipe with three screws.
5. Install the remaining lengths of pipe one on top of the
other to the finished height of the chimney connector and
secure to each other.
130715-24

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents