5.10
Detector heating FDBH291
5.10.1
Installation of the detector heating unit
Building Technologies
Fire Safety & Security Products
When the detector is exposed to icing or moisture condensation (e.g. in cooling
rooms, attics, loading ramps) the detector heating unit FDBH291 is installed in the
base. The detector heating unit increases the detector temperature by
approximately 2 °C over the ambient temperature and thus avoids moisture
condensation on the detector.
To ensure IP protection, the base is always mounted together with the base
attachment humid FDB293.
DBZ1190-AA
1
Installation of the detector heating unit FDBH291
1 Micro terminals
2 Base attachment humid
Mounting / Installation
FDB293
2
FDB2x1
FDB2x1-AA
FDB2x2
3
FDBH291
4
3 Detector base
4 Detector heating unit