Connection Diagram (Ms8); Use Of Unshielded Cables - Siemens FDOOT241-9 Technical Manual

Automatic fire detectors
Hide thumbs Also See for FDOOT241-9:
Table of Contents

Advertisement

Mounting / Installation
5.13.3

Connection diagram (MS8)

5.13.3.1

Use of unshielded cables

76
Building Technologies
Fire Safety & Security Products
Variant B:
1. Connect the positive pole of the external alarm indicator to the positive pole for
the alarm indicator on the detector.
2. Leave the negative pole for the alarm indicator on the detector unoccupied.
3. Connect the negative pole of the external alarm indicator with the negative
terminal on the input side of the collective line on the detector via an auxiliary
terminal DBZ1190-xx.
4. Connect the shielding of the collective line with the shielding of the connection
cable to the external alarm indicator via an auxiliary terminal DBZ1190-xx.
On an MS8 detector line an external alarm indicator may be connected to only one
detector.
Guideline
The connection is established from base to base using twisted or non-twisted
wire pairs.
-
-
-
+
+
+
+
1
-
Connection diagram for MS8 detector line with and without external alarm indicators (without
shielded cables)
1 Control panel
2 Base adapter FDB281 (with fitted
detector base FDB221)
-
-
2
+
+
+
LINE
3
3 External alarm indicator DJ119x
-
-
+
+
007004_k_en_--
16.04.2009
-
-
+