Mounting / Installation
5.13.2.1

Use of unshielded cables

74
Building Technologies
Fire Safety & Security Products
Guideline
The connection is established from base to base using twisted or non-twisted
wire pairs.
-
-
-
+
+
+
+
1
-
A
Connection diagram for collective detector line with and without external alarm indicators
(without shielded cables)
1 Control panel
2 Detector base FDB201/FDB201-AA,
FDB202
Notes
Standard wiring:
The external alarm indicator is connected to the positive and negative poles of
each detector.
Wire-saving cabling:
The external alarm indicators are connected as follows:
‒ The external alarm indicator must be connected to the positive and negative
poles of at least one detector (A).
‒ The external alarm indicator must be connected to the positive pole of every
other detector (B).
‒ The external alarm indicator need not be connected to the negative pole of
each other detector (C).
The wire-saving cabling for external alarm indicators is not admissible for new
installations.
2
-
-
+
+
+
LINE
B
3
3 External alarm indicator DJ119x
4 End-of-line depending on control
panel
-
-
+
+
4
007004_k_en_--
16.04.2009
-
-
+
C