4.4.2
Wide-spectrum smoke detector FDO221
4.4.2.1
Description
4.4.2.2
Application
No. Name
Risk of injury to
persons
small ...
large
2
Standard
3
Standard Plus
4.4.2.3
Specification
Building Technologies
Fire Safety & Security Products
Standard (2):
The priority of the 'Standard' parameter set is set to robust response. It is thus
particularly suited to application in rooms where few deceptive phenomena such as
cigarette smoke can be expected.
Standard Plus (3):
This parameter set is both fast and sensitive. It is thus especially suited to rooms
without deceptive phenomena, where the priority is on early fire detection.
Concentration
of valuable
items
low...
high
No.
Name
2
Standard
3
Standard Plus
All parameter sets meet the standard EN 54-7.
Room
Deceptive
geometry
phenomena
simple...
few...
complex
many
Response time [s]
60
50
Project engineering
Risk of fire
Critical fire size
small ...
small ...
large
medium
Sensitivity [%/m]
2.8
2
007004_k_en_--
16.04.2009