Specification - Siemens FDOOT241-9 Technical Manual

Automatic fire detectors
Hide thumbs Also See for FDOOT241-9:
Table of Contents

Advertisement

4.3.1.3

Specification

No.
Name
8
High Suppression
(as of ES ≥30)
2
5
Suppression
7
High Compensation
0
High Compensation
1
(only FDnet
operation)
0
High Compensation
1
(only collective
operation from ES ≥
13)
2
Robust
0
Insensitive
1
(only collective
operation up to ES <
13)
4
Balanced
0
Sensitive
1
(only MS8 operation)
6
Fast Response
9
High Sensitive Fast
(from ES ≥ 30)
14
Application-specific parameter sets
15
Building Technologies
Fire Safety & Security Products
The following table shows the characteristics and application fields of the
parameter sets of the neural fire detectors FDOOT241-9 and FDOOT241-8.
Optical
Typ. response
Sensitivity,
time
open fire
from - typ. - to
[s]
[%/m]
60 - 80 - 360
2,3
90 -160 - 760
3,2
80
3,2
80
3,2
80
3,2
80
3,2
30
3,2
40 - 64 - 300
2,3
30
1,6
20 - 30
1,6
20 - 30
0,8
= Delivery status; only selectable in collective operation and MS8 operation.
1
Note chapter '4.3.1.1 Description', 'High Suppression (8)' paragraph.
2
Applicable with fast temperature increases >10 K/min.
3
All parameter sets except for 8 comply with standards EN 54-7 and CEA 4021.
Thermal
Sensitivity,
Static
smoldering fire
activation
temperature
[%/m]
[°C]
8
80
11,4
80
11,4
80
11,4
80
11,4
80
11,4
80
11,4
80
8
80
5,6
80
5,6
80
2,8
60
Project engineering
Differential
Differential
activation
activation
temperature
possible from:
3
∆T [K]
[°C]
25
30
29
30
29
30
29
30
29
30
29
30
29
30
25
30
22
30
22
3
16
3
007004_k_en_--
16.04.2009
45

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fdoot221Fdoot241-8Fdo241Fdo221Fdt241Fdt221

Table of Contents