Download Print this page

Siemens FDOOT441 Installation Instructions

Multi-criteria fire detector

Advertisement

Quick Links

Installation Instructions
Model FDOOT441
Multi-Criteria Fire Detector
These instructions are written in accordance with the installation
guidelines of NFPA 72, National Fire Alarm Code. The model
FDOOT441 detector (shown in Figure 1) meets the VEWFD (Very
Early Warning Fire Detector) classification and sensitivity
requirements of NFPA 76 (Standard for the Fire Protection of
Telecommunications Facilities) incorporating a programmable
"Alert" (Pre-Alarm) sensitivity threshold of 0.2%/ft obscuration
and an "Alarm" sensitivity threshold of 1.0%/ft obscuration.
CAUTION
Detection Device Storage
DO NOT install this detection device until all construction
is completed.
DO NOT store this detection device where it can be
contaminated by dirt, dust, or humidity.
DETECTOR PLACEMENT
Although no specific spacings are set for the detectors used for
a clean air application, for multi-criteria fire detection use 30
foot center spacing (900 sq ft) from NFPA Standard 72 initiating
devices chapter, if practical, as a guide or starting point for a
detector installation layout. This spacing, however, is based on
ideal conditions–smooth ceiling, no air movement, and no
physical obstructions. In some applications, therefore,
considerably less area is protected adequately by each smoke
detector. This is why it is mandatory to closely follow the
installation drawings. In all installations place the detector on
the ceiling, a minimum of 6 inches from a side wall, or on a wall,
12 inches from the ceiling.
For FM Approved installations, this device has an RTI rating of QUICK.
For thermal detection, use the matrix below:
S
p
a
c
n i
, g
F
e
t e
T
e
m
p
e
a r
u t
e r
5
0
1
3
, 5
1
4
, 5
1
5
, 5
6
0
1
3
, 5
1
4
, 5
1
5
, 5
6
0
1
3
, 5
1
4
, 5
7
0
1
3
, 5
1
7
0
1
3
5
A6V10324655_en--_e
0
R
t a
n i
, g
F
W
t i
/ h
W
i
h t
o
t u
G
u
a
d r
1
6
, 5
1
7
5
W
i
h t
a
n
d
W
i
h t
o
t u
1
6
, 5
1
7
5
W
i
h t
o
t u
G
u
a
d r
1
5
5
W
i
h t
G
u
a
d r
4
5
W
i
h t
o
t u
G
u
a
d r
W
i
h t
G
u
a
d r
Figure 1
FDOOT441
If you have any questions regarding detector placement, follow
the drawings provided or approved by Siemens Industry, Inc.,
or by its authorized distributors. This is extremely important! The
detector placements shown on these drawings were chosen after
a careful evaluation of the area that is protected. Such factors
as air currents, temperature, humidity, pressure, and the nature
of the fire load were carefully considered. Especially noted were
the room or area configuration and the type of ceiling (sloped or
flat, smooth or beamed). Siemens Industry, Inc.'s extensive
experience in the design of the system assures the best detector
placement by following these drawings.
TO AVOID NUISANCE ALARMS
Do not locate the detectors where excessive smoke
concentrations exist under normal conditions, or in areas of
prolonged high relative humidity where condensation occurs.
Do not locate the detectors next to an oil burner, kitchen, or
garage where exhaust fumes can trigger an alarm. Other causes
of false alarm are dust accumulation, heavy concentrations of
steam, heavy pipe or cigar smoke, and certain aerosol sprays.
AIR CURRENTS
Before a detector can sense a fire, the products of combustion
or smoke must travel from the fire to the detector. This travel is
especially influenced by air currents; therefore, consider air
movement when designing the system. While combustion
products tend to rise, drafts from hallways, air diffusers, fans,
etc., may help or hinder the travel of combustion products to the
detector. When positioning a detector at a particular location,
give consideration to windows and doors, both open and closed,
to ventilating systems, both in and out of operation, and to other
factors influencing air movement. Do not install a detector in the
air stream of a room air supply diffuser. It is better to position a
detector closer to an air return.
The distance that products of combustion or smoke travel from
M
o
d
l e
a fire to the detector is not usually the shortest linear route.
Combustion products or smoke usually rise to the ceiling, then
G
u
a
d r
spread out. Average ceiling heights of 8 to 10 feet do not
abnormally affect detector response. High ceilings, located in
churches, warehouses, auditoriums, etc., do affect detector
response and should be considered.
Siemens Industry
Siemens
Siemens
Industry
Industry
Industry, , , , , Inc.
Siemens
Siemens
Industry
Building T T T T T ec
Building
Building
ec
echnologies Di
ec
hnologies Division
hnologies Di
hnologies Di
Building
Building
ec
hnologies Di
Inc.
Inc.
Inc.
Inc.
vision
vision
vision
vision

Advertisement

loading

Summary of Contents for Siemens FDOOT441

  • Page 1 NFPA 72, National Fire Alarm Code. The model the drawings provided or approved by Siemens Industry, Inc., FDOOT441 detector (shown in Figure 1) meets the VEWFD (Very or by its authorized distributors. This is extremely important! The Early Warning Fire Detector) classification and sensitivity...
  • Page 2 Each detector provides pre-programmed parameter sets which travel, joists and beams can slow the movement of heated air can be selected by the panel. The FDOOT441 provides two and smoke, while pockets between them can contain a reduced different alarm channels: multi-criteria (UL268) and direct in- level of smoke.
  • Page 3 TO REMOVE DETECTOR HEAD: SENSITIVITY MEASUREMENT • Loosen locking screw, if installed. Then rotate the detector The sensitivity of FDOOT441 detectors can be tested individually counterclockwise until stop is reached. using the DPU. Refer to the DPU Manual, P/N 315-033260. The •...
  • Page 4 SUPERVISED AND POWER LIMITED *The relay contacts are shown after System reset, which represents the non-alarm condition. **FDOOT441 is a polarity insensitive detector. Line 1 and Line 2 can be either line of the loop. ***FDOOT441 is NOT compatible with the DB-HR base.