Installation

1 . Before opening the thermostat housing set adjustment button to
minimum temperature, viz . -10˚C .
2 . When installing in bathrooms etc ., the minimum distance to water
installations must be observed and must comply with current regula-
tions for electric installations .
3 . The stamped punchings for diaphragm nipple are removed with a
screwdriver and a hammer .
4 . The thermostat is mounted vertically on a wall . The screw holes must
be sealed with the enclosed plugs .
5 . If the sensor is to be built in or exposed to pressure it should be
placed in an installation pipe .
6 . Installation of thermostat see diagram . Choose function (heating/
cooling) .
7 . After closing the thermostat housing, check that adjustment button
can be adjusted within full temperature range, i .e . from -10˚C to
+50˚C .
02/2007
VIFZK102
3