Principal Parts And Functions - Mitsubishi Electric PUHY-(E)P200 Service Handbook

Hide thumbs Also See for PUHY-(E)P200:
Table of Contents

Advertisement

[ VI Refrigerant Circuit ]

[2] Principal Parts and Functions

1. Outdoor unit
Part
Symbols
name
(functions)
Com-
MC1
pressor
(Comp1)
High
63HS1
pres-
sure
sensor
Low
63LS
pres-
sure
sensor
Pres-
63H1
sure
switch
HWE07010
Notes
Usage
Adjusts the amount of circulating
refrigerant by adjusting the operat-
ing frequency based on the oper-
ating pressure data
1) Detects high pressure
2) Regulates frequency and pro-
vides high-pressure protec-
tion
1) Detects low pressure
2) Provides low-pressure pro-
tection
1) Detects high pressure
2) Provides high-pressure pro-
tection
- 74 -
Specifications
200 - 250 models
Low-pressure shell scroll
compressor
Wirewound resistance
20°C[68°F] : 0.981ohm
300 - 450 models
Low-pressure shell scroll
compressor
Wirewound resistance
20°C[68°F] : 0.583ohm
Pressure
63HS1
0~4.15 MPa [601psi]
Vout 0.5~3.5V
1 2 3
0.071V/0.098 MPa [14psi]
Pressure [MPa]
Con-
=1.38 x Vout [V]-0.69
nector
Pressure [psi]
=(1.38 x Vout [V] - 0.69) x 145
GND (Black)
1
2
Vout (White)
3
Vcc (DC5V) (Red)
Pressure
63LS
0~1.7 MPa [247psi]
Vout 0.5~3.5V
1 2 3
0.173V/0.098 MPa [14psi]
Pressure [MPa]
Con-
=0.566 x Vout [V] - 0.283
nector
Pressure [psi]
=(0.566 x Vout [V] - 0.283) x 145
1
GND (Black)
2
Vout (White)
3
Vcc (DC5V) (Red)
4.15MPa[601psi] OFF setting
Check method
GB

Hide quick links:

Advertisement

Table of Contents
loading