[ VII Control ]
-15- DEMAND Control
Cooling/heating operation can be prohibited (Thermo-OFF) by an external input to the indoor units.
When DIP SW4-4 is set to ON, the 4-step DEMAND control is enabled. While this control is enabled, the NIGHTMODE will
be disabled.
Eight-step demand control is possible in the system with two outdoor units.
Twelve-step demand control is possible in the system with three outdoor units.
Refer to Chapter 2 -[3]- (7) "Various types of control using input-output signal connector on the outdoor unit (various connec-
tion options)" for details.(page 23)