Mitsubishi Electric PUHY-(E)P200 Service Handbook page 128

Hide thumbs Also See for PUHY-(E)P200:
Table of Contents

Advertisement

[ VIII Test Run Mode ]
Ambient
tempera-
ture
Indoor
unit
Operating
conditions
Piping
Fan speed
Amount of refrigerant
Electric current
Outdoor
Voltage
unit
Compressor frequency
Indoor unit
LEV open-
SC (LEV1)
ing
LEV2
High pressure (after O/S)/low
Pressure
pressure (before accumulator)
Outdoor
unit
Temp. of
each sec-
tion
Indoor
unit
HWE07010
Operation
Indoor
DB/WB
Outdoor
No. of connected
units
Unit
No. of units in opera-
tion
Model
Main pipe
Branch pipe
m [ft]
Total pipe length
[lbs-oz]
Pulse
MPa
[psi]
Discharge (TH4)
Heat exchanger out-
let (TH3)
Accumulator inlet
Accumulator outlet
°C [°F]
Compressor inlet
Compressor shell
bottom
LEV inlet
Heat exchanger
outlet
PUHY-P300YHM-A
20°C/ - [68°F/ - ]
7°C/6°C [45°F/43°F]
3
3
-
100/100/100
5 [16-3/8 ]
10 [32-3/4 ]
35 [114-13/16 ]
-
Hi
kg
15
[33]
A
15.0
V
400
Hz
81
332/332/332
0
-
2.78/0.61 [403/88]
82 [180]
-3 [27]
-3 [27]
-3 [27]
-3 [27]
40 [104]
39 [102]
80 [176]
- 119 -
Outdoor unit model
PUHY-P350YHM-A
20°C/ - [68°F/ - ]
7°C/6°C [45°F/43°F]
3
3
100/125/125
5 [16-3/8 ]
10 [32-3/4 ]
35 [114-13/16 ]
Hi
15
19.3
400
101
332/406/406
0
-
2.81/0.57 [408/83]
82 [180]
-3 [27]
-3 [27]
-3 [27]
-3 [27]
40 [104]
39 [102]
80 [176]
[33]
GB