[ II Restrictions ]

[7] An Example of a System to which both MA Remote Controller and M-NET Remote Controller are connected

(1) Sample control wiring
(2) Cautions
1) Be sure to connect a system controller.
2) M-NET remote controller and MA remote controller can-
not both be connected to the same group of indoor units.
3) Assign to the indoor units connected to the MA remote
controller addresses that are smaller than those of the in-
door units that are connected to the M-NET remote con-
troller.
4) No more than 2 M-NET remote controllers can be con-
nected to a group of indoor units.
5) No more than 2 MA remote controllers can be connected
to a group of indoor units.
6) Do not connect the terminal blocks (TB5) on the indoor
units that are connected to different outdoor units with
each other.
7) Replace the power jumper connector of the control board
from CN41 to CN40 on only one of the outdoor units.
8) Provide an electrical path to ground for the S terminal on
the terminal block for centralized control on only one of
the outdoor units.
9) A transmission booster must be connected to a system
in which the total number of connected indoor units ex-
ceeds 20.
10) A transmission booster is required in a system to which
more than 16 indoor including one or more indoor units
of the 200 model or above are connected.
11) When a power supply unit is connected to the transmis-
sion line for centralized control, leave the power jumper
connector on CN41 as it is (factory setting).
HWE07010
L11
CN41
Leave the male
Leave the male
connector on
connector on
SW2-1 OFF ON
CN41 as it is.
CN41 as it is.
SW2-1 OFF ON
SW2-1 OFF ON
OS2
OS1
53
52
TB3
TB3
M1 M2
M1 M2
M1 M2
TB7
TB7
M1 M2
S
M1 M2
S
M1 M2
Not
Not
Connect
Connect
L21
Leave the male
Leave the male
Leave the male
connector on
connector on
connector on
CN41 as it is.
CN41 as it is.
CN41 as it is.
SW2-1 OFF ON
SW2-1 OFF ON
SW2-1 OFF ON
OS2
OS1
56
55
TB3
TB3
M1 M2
M1 M2
M1 M2
TB7
TB7
M1 M2
S
M1 M2
S
M1 M2
Not
Not
Connect
Connect
L12
CN40 Replace
Group
OC
IC
01
51
TB5
TB15
TB3
M1 M2
1 2
M1 M2
S
TB7
S
Connect
A B
MA
L22
Group
Group
OC
IC
03
54
TB5
TB5
TB15
TB3
M1 M2
S
1 2
M1 M2
TB7
S
A B
A B
Not
Connect
104
MA
RC
Note1 When only the LM adapter is connected,
Note2 LM adapters require the power supply
Note1
System controller
A B S
(3) Maximum allowable length
1) Indoor/outdoor transmission line
Same as [5] 3.
2) Transmission line for centralized control
Same as [5] 4.
3) MA remote controller wiring
Same as [5] 1.
4) M-NET remote controller wiring
Same as [5] 1.
- 40 -
Group
IC
IC
02
06
TB5
TB15
TB5
TB15
1 2
M1 M2
1 2
S
S
A B
106
RC
IC
IC
04
05
TB15
TB5
TB15
S
1 2
M1 M2
1 2
S
leave SW2-1 to OFF (as it is).
capacity of single-phase AC 208/230V.