[ VIII Test Run Mode ]

[7] Standard Operation Data (Reference Data)

1. Single unit
(1) Cooling operation
Ambient
tempera-
ture
Indoor
unit
Operating
conditions
Piping
Fan speed
Amount of refrigerant
Electric current
Outdoor
Voltage
unit
Compressor frequency
Indoor unit
LEV open-
SC (LEV1)
ing
LEV2
High pressure (after O/S)/low
Pressure
pressure (before accumulator)
Outdoor
unit
Temp. of
each sec-
tion
Indoor
unit
HWE07010
Operation
Indoor
DB/WB
Outdoor
No. of connected
units
No. of units in opera-
tion
Model
Main pipe
Branch pipe
m [ft]
Total pipe length
[lbs-oz]
Pulse
MPa
Discharge (TH4)
Heat exchanger out-
let (TH3)
Accumulator inlet
Accumulator outlet
SCC outlet (TH6)
°C [°F]
Compressor inlet
Compressor shell
bottom
LEV inlet
Heat exchanger
outlet
PUHY-P200YHM-A
27°C/19°C [81°F/66°F]
35°C/ - [95°F/ - ]
2
Unit
2
-
100/100
5 [16-3/8 ]
10 [32-3/4 ]
25 [82]
-
Hi
kg
11 [24]
A
9.1
V
400
Hz
52
325/325
80
-
[psi]
2.77/0.74 [402/107]
89 [192]
44 [111]
7 [45]
7 [45]
22 [72]
19 [66]
47 [117]
19 [66]
6 [43]
- 115 -
Outdoor unit model
PUHY-P250YHM-A
27°C/19°C [81°F/66°F]
35°C/ - [95°F/ - ]
2
2
125/125
5 [16-3/8 ]
10 [32-3/4 ]
25 [82]
Hi
11 [24]
12.3
400
65
387/387
100
-
3.11/0.86 [451/125]
85 [185]
44 [111]
7 [45]
7 [45]
24 [75]
19 [66]
38 [100]
19 [66]
6 [43]
GB