[ VIII Test Run Mode ]
Ambient
tempera-
ture
Indoor
unit
Operating
conditions
Piping
Fan speed
Amount of refrigerant
Electric current
Outdoor
Voltage
unit
Compressor frequency
Indoor unit
LEV open-
SC (LEV1)
ing
LEV2
High pressure (after O/S)/low
Pressure
pressure (before accumulator)
Outdoor
unit
Temp. of
each sec-
tion
Indoor
unit
HWE07010
Operation
Indoor
DB/WB
Outdoor
No. of connected
units
No. of units in opera-
tion
Model
Main pipe
Branch pipe
m [ft]
Total pipe length
[lbs-oz]
Pulse
MPa
Discharge (TH4)
Heat exchanger out-
let (TH3)
Accumulator inlet
Accumulator outlet
SCC outlet (TH6)
°C [°F]
Compressor inlet
Compressor shell
bottom
LEV inlet
Heat exchanger
outlet
PUHY-P250YHM-A
Unit
-
-
kg
A
V
Hz
65
159
1400
[psi]
3.10/0.78 [450/113]
91 [196]
47 [117]
7 [45]
7 [45]
27 [81]
19 [66]
42 [108]
- 122 -
Outdoor unit model
PUHY-P550YSHM-A
PUHY-P300YHM-A
27°C/19°C [81°F/66°F]
35°C/ - [95°F/ - ]
6
6
20/100/100/100/125/125
5 [16-3/8]
10 [32-3/4]
65 [213-1/4]
Hi
25 [55]
29.4
400
222/325/325/325/387/387
3.10/0.74 [450/107]
89 [192]
47 [117]
27 [81]
19 [66]
42 [108]
19 [66]
6 [43]
71
237
1400
7 [45]
7 [45]
GB