Mitsubishi Electric PUHY-(E)P200 Service Handbook page 86

Hide thumbs Also See for PUHY-(E)P200:
Table of Contents

Advertisement

[ VI Refrigerant Circuit ]
2. Indoor Unit
Part
Symbol
Name
(functions)
Linear
LEV
expan-
sion valve
Ther-
TH1
mistor
(Suction air
temperature)
TH2
(Pipe temper-
ature)
TH3
(Gas pipe
temperature)
TH4
Outdoor air
temperature)
Temperature
sensor (In-
door air tem-
perature)
HWE07010
Notes
Usage
1) Adjusts superheat at the
indoor heat exchanger
outlet during cooling
2) Adjusts subcool at the
heat exchanger outlet of
the indoor unit during
cooling
Indoor unit control (Thermo)
1) Indoor unit control (Frost
prevention, Hot adjust)
2) LEV control during heat-
ing operation (subcool
detection).
LEV control during cooling op-
eration (superheat detection)
Indoor unit control (Thermo)
Indoor unit control (Thermo)
Specification
DC12V
Opening of stepping motor
driving valve 0-(1400) puls-
es
R
=15k
0
R
=3460
0/80
Rt =
15exp{3460(
273+t
0°C [32°F]:15kohm
10°C [50°F] :9.7kohm
20°C [68°F]:6.4kohm
25°C [77°F] :5.3kohm
30°C [86°F] :4.3kohm
40°C [104°F] :3.1kohm
- 77 -
Check method
Refer to the section
"Continuity Test with a
Tester".
Continuity between
white, red, and or-
ange.
Continuity between
yellow, brown, and
blue.
White
Red
Orange
Yellow
Resistance check
1
1
-
)}
273
Brown Blue
GB