[8] Restrictions on Pipe Length

(1) End branching
P200 - P450 models
Outdoor unit
A
First branch
(Branch joint)
Branch joint
Length
Total pipe length
Total pipe length (L) from the outdoor unit to the
farthest indoor unit
Total pipe length from the first branch to the far-
thest indoor unit ( )
Height
Between indoor and
difference
outdoor units
Between indoor units
HWE07010
D
L
B
C
a
b
1
Indoor
2
Indoor
3
Operation
Outdoor unit above in-
door unit
Outdoor unit below in-
door unit
Indoor
c
Indoor
Pipe sections
A+B+C+D
+a+b+c+d+e+f
A+B+C+c or
A+D+f
B+C+c or
D+f
H
H'
h
- 42 -
Branch header
cap
e
d
f
Indoor
Indoor
4
6
5
Unit: m [ft]
Allowable length of
pipes
1000 [3280] or less
165 [541] or less
(Equivalent length 190
[623] or less)
40 [131] or less
50 [164] or less
40 [131] or less
15 [49] or less