weighing approx. 50% of the weight of the generating
set. A heavy base plate is available as an optional
installation kit. (Ref. to fig. 24, item 62).
2.2.2

Further recommendations

Whisper generating sets are standard equipped with a
"GRP" (Glass Reinforced Plastic) sound cover. The ca-
nopy has been designed to give an effective sound insu-
lation. For optimum sound and vibration dampening, the
following factors should be considered.
1 In larger vehicles a separate and insulated space for
the generator will help to damp the noise even
further.
2 Avoid mounting the generating set in close proximity
to thin walls or floors as that may resonate.
3 Sound dampening is extremely poor if the generating
set is mounted on a light weight flimsy surface such
as plywood which will only amplify vibrations. If
mounting on a thinner surface cannot be avoided, this
should at least be reinforced with stiffening struts or
ribbing. If possible, holes should be drilled or cut
through the surface to help reduce the resonance.
Covering the surrounding walls and floors with a
heavy coating plus foam will improve the situation.
WHISPER 3,5 / 3000RPM
1
Fuel lift pump cable (41)
2
battery connection (positive) (3)
3
Connectors radiator temperature switch (13)
4
oil pipe out (42)
5
Cooling water out (10)
6
Battery connection (negative) (4)
7
Exhaust connection (26)
8
Oil pipe in (43)
9
Cooling water in (11)
10
Fuel pipe return (9)
11
AC 230V wiring (5)
12
Remote control cable (33)
13
Fuel pipe inlet (8)
July 2005 / MOBILE WHISPER 3,5 / EN
4 Never connect the base of the generating set directly
to bulkheads, walls or tanks.
2.3

VENTILATION

The generating set normally draws combustion air from
the engine room. A full enclosure with natural ventilation
must have ventilation openings of adequate size and
location to enable the generating set to operate without
overheating. To allow an ample supply of air within the
temperature limits of the generating set an opening of at
least 100 cm
2
is required. The radiator need its own
airflow. (Refer to par. 2.4.2 - 4).
Air inlets should be louvered, where appropriate, to pro-
tect the generating set from water spray.
2.4

CONNECTIONS

The generating set comes with all supply lines and output
cables (i.e. electric cables, cooling water an oil connec-
tions, exhaust, fuel lines etc.) already connected to the
engine and alternator. The supply lines are led through the
capsule's base. The connections are marked as shown in
fig. 5.
ATTENTION!
Before working (installation) on the system
read the section safety instructions.
1
2
3
4
5
6
7
8
9
10
11
12
13
INSTALLATION