30 | Installation instructions

8.4 Program values

This section describes details on programming the appliance.
For most applications the fact
robust and stable operation.
Program Description
P1
Maximum Power N. Gas: 40
P2
Minimum Power N. Gas: 8
P3
Remote
Controls installed
P4
Access to
Diagnostic Mode
P5
Cascade Mode
P6
Temperature Unit °C
P7
Appliance Type nO
P8
Back light
P9
Fan Purge
PH
Cascading type IC
PC
Master/Slave
mode
Table 12
6 720 800 095 (2014/05)
ory default values will provide
Factory default
Min
21
LPG: 37
N. Gas: 8
LPG: 7
LPG: 7
_0
_0
E
0d
nO
nO
°F
Cd
(condensing)
dE
dE
IC
CS
CS
CAUTION: Misadjusted program values
can lead to appliance malfunction, errors,
and service calls.
Max
Comment
N. Gas: 40
See chapter 8.2.
LPG: 37
Note: reducing P1 values below maximum
will reduce maximum power of the
appliance.
20
See chapter 8.2.
6
See chapter 4.6.
10f
See chapter 8.5.
CC
To activate the cascade mode it's necessary
to install the "kit cascade" (cod. 7 736 500
272)
°C
See chapter 8.5.
nO
Condensing / Non-condensing
note: incorrect setting will cause errors.
On
dE: turns back light o after 60 seconds
from last button pushed.
ON: turns backlight on permanently.
Runs secondary fan and primary fan when
P9 is selected by depressing the "P" - button
SC
This menu is only available when cascade
mode is selected CC.
Cn
Therm 6000S