Bosch Therm 6000 S Installation And Operating Instructions Manual page 29

Table of Contents

Advertisement

Repeat steps 1 and 2 as necessary until CO
within the speci ed ranges.
As soon as the levels of CO
CO corresponds to the limits of the Table 10 . If the values
exceed the limits, it is necess ary to verify the ventilation
system and heat exchanger.
CO
2
Natural gas
Max. input
P1
from 7.3% to 7.9%
Min. input
P2
from 2.7% to 3.1%
Butane
Max. input
P1
from 8.6% to 9.2%
Min. input
P2
from 3.0% to 3.4%
Note: Values above are for climate controlled conditions.
Inputs such as gas pressure, heating value of the gas,
humidity and temperature of co
and CO
values. Changes in these inputs can result in
2
di erent CO and CO
values on the same appliance.
2
Table 10 CO
& CO target numbers
2
End of adjustments
Record the nal values in Table 11 .
Program
CO
values measured
2
P1
______________ %
P2
______________ %
Table 11
Reassemble all parts in reverse order:
Return slotted screw cover to original position and tighten
the philips screw, Fig. 45.
Reinstall Torx protection cover, Fig. 46.
Remove CO
analyser probe and reinstall athead screw
2
with gasket in exhaust collar.
Press ON/OFF button to turn OFF the heater.
Press ON/OFF button to turn ON the heater.
Heater is ready for normal operation.
Therm 6000S
values are
2
are correct, verify the values of
2
Máx. CO level
range (%)
(measured)
< 250 ppm
< 60 ppm
< 250 ppm
< 60 ppm
mbustion air all impact CO
Date
Installation instructions | 29
6 720 800 095 (2014/05)