2.8 Calculation for Standby Battery Requirement

Step
Device
1
MR-2602
Zone 1
Zone 2
NAC 1
2
3
NAC 2
MR-2605-T
4
MR-2605-AT
MR-2806
MR-2605-R3
5
AUX+
6
Total 'standby' and 'alarm' current:
7
Divide 'standby' mA and 'alarm' mA by 1000:
8
Select 'standby' time required (24 or 60 Hr.):
Standby Amp-Hr. - multiply 8 × 7 = (Amps × Hr.):
9
10
Select 'alarm' time required
11
Alarm Amp-Hr. - multiply 7 × 10 = (Amps × Hr.):
12
Total Amp-Hr = standby Amp-Hr (9) + alarm Amp-Hr. (11):
13
Multiply the total Amp-Hr. by the safety margin:
Total battery Amp-Hr required to support the system:
14
Select a battery with an Amp-Hr. rating that is equal to or larger than the calculated minimum Amp-
Note:
Hr. battery required.
Current per
device (mA)
Standby:
90
Alarm:
365
Standby:
Alarm:
69
Standby:
Alarm:
69
Alarm:
Alarm:
Standby:
15
Alarm:
15
Standby:
15
Alarm:
25
Standby:
45
Alarm:
60
Standby:
0
Alarm:
24
Standby:
Alarm:
(0.08 or 0.5)
:
MR-2602 Installation & Operator's Manual
Number
Standby
of device
Current (mA)
x
1
= 90
x
1
=
x
=
x
1
=
x
=
x
1
=
=
x
=
x
x
x
x
x
x
x
x
=
x
x
=
x
=
mA
Amp
Hr.
1.20
Total
Total Alarm
Current
(mA)
365
69
mA
Amp
Amp-Hr.
Hr.
Amp-Hr.
Amp-Hr.
Amp-Hr.
7