Viewing The Event Buffer - Secutron MR-2602 Installation Manual

Table of Contents

Advertisement

ALARM
SUPV
Do not
default (Z2)
(Factory default
)
Default to factory
program (Z2)

6.3 Viewing the Event Buffer

1. Enter the programming mode by pressing and holding the Walk Test switch for 2 seconds.
2. Press any switch. To silence the trouble buzzer and enter the Section 0 programming.
3. Press and hold the Lamp Test switch for 2 seconds.
4. The Common Supervisory LED flashes to indicate the View Buffer mode.
5. Events are shown from the most recent to the oldest.
6. See the event table below which indicates the LED patterns used to indicate various events.
7. To advance to the next event press the Silence Trouble switch.
8. Once all 20 events have been viewed, the next Silence Trouble keypress will exit the view buffer mode
and return to the Section 0 programming. To exit the programming mode, press and hold for 2 seconds the
Walk Test switch.
9. Pressing the Silence Signal switch at any time will cause the system to exit the View Buffer mode. The
buzzer will sound. Press any button to go to the Section 0 programming mode.
50/60 Hz Option
Reset Section Programming (All common trouble LEDs flashing)
To Enter this Programming Section
1. Enter the installer programming mode, section 0
2. Press and hold the System Reset button for 2 seconds. The Z1 ALM
LED and TRB LED will be ON and all the System Trouble LEDs will
flash.
To Remove Module
Physically remove the module from the system and enter the reset section
programming as described above. Press the 'Silence Alarm' button until the
Z1 SUPV LED is ON. Press the 'Silence Trouble' button to exit this section.
Upon exit, the system will reset the 'supervision' field for all the modules
currently connected to the 'secur-bus'.
To Add a Module
Just connect it to the system and it will auto-enroll within one minute.
To Default the System
Enter the reset section programming as described above. Press the 'Silence
TRB
Trouble' button until the Z2 ALM LED is ON and Z2 TRB LED is ON. Press
the 'Silence Alarm' button until the Z2 SUPV LED is ON. Press the 'Silence
Trouble' to exit this section. Upon exit, the system will reset all of the panel
programmable parameters to their factory default state. Please note that the
'supervision' field will be reset as well.
MR-2602 Installation & Operator's Manual