Secutron MR-2306-AT Wiring & Installation Manual

Remote annunciator
Hide thumbs Also See for MR-2306-AT:

Advertisement

Quick Links

M R - 2 3 0 6 - A T
Remote Annunciator
W
IRING &
I
NSTALLATION
M
ANUAL
Rev i sion 1
Document #: LT-648SEC
WARNING : This manual contains information on limitations
regarding product use and function and information on the
limitations as to liability of the manufacturer. The entire
manual should be read carefully.

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the MR-2306-AT and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Secutron MR-2306-AT

  • Page 1 M R - 2 3 0 6 - A T Remote Annunciator IRING & NSTALLATION ANUAL Rev i sion 1 Document #: LT-648SEC WARNING : This manual contains information on limitations regarding product use and function and information on the limitations as to liability of the manufacturer.
  • Page 3: Table Of Contents

    MR-23006-AT Remote Multiplex Annunciator Panel Wiring and Installation Manual Table of Contents Introduction ..........................1 Technical Support ......................... 1 Installation Instruction ......................2 Controls & Displays....................... 2 Wiring Instruction ........................3 Dip Switch Settings ....................... 4 Jumper Selection ........................4 Specifications &...
  • Page 5: Introduction

    Note: For ULC S527 applications the MR-2306-AT is an ancillary display device. Technical Support For all technical support inquiries, please contact Secutron’s Technical Support Department between 8 A.M. and 5 P.M. (EDT) Monday through Friday, excluding holidays. Local Phone: 905-695-3545...
  • Page 6: Installation Instruction

    For more details, refer to the manual of the fire alarm control panel that the annunciator will be connected to. • The MR-2306-AT has a keyswitch to enable the four slide-switch controls. The key should be appropriately secured.
  • Page 7: Wiring Instruction

    FA Panel to the first Annunciator, then the next Annunciator, and so on. No star-wiring or T-tapping is allowed. Each MR-2306-AT Annunciator Module has a 120 ohm End-of-Line Resistor on its RS- 485 Output terminals. This is removed on all except the last wired Module.
  • Page 8: Dip Switch Settings

    Introduction Dip Switch Settings Each annunciator needs to be assigned a unique, sequential address via DIP switches SW1-1, SW1-2, and SW1-3. DIP switch SW1-4 is used to allow disabling of some front panel slide switches. SW1-1 Address A0 Three digit address of the annunciator (address SW1-2 Address A1 >...
  • Page 9: Specifications & Features

    MR-23006-AT Remote Multiplex Annunciator Panel Wiring and Installation Manual Specifications & Features Enclosure A standard 4-gang Electrical Box is used. Electrical Specifications • 24 VDC nominal voltage • Slide-Switch Controls, LED indicators, and Keyswitch to enable Controls. • Local Buzzer, Indicators (AC-On, Common Trouble, Signal Silence), and Controls (System Reset, Lamp Test, Buzzer Silence, Signal Silence).
  • Page 10: Warranty & Warning Information

    Warranty & Warning Information Warranty & Warning Information Warning Please Read Carefully Note to End Users: This equipment is subject to terms and conditions of sale as follows: Note to Installers This warning contains vital information. As the only individual in contact with system users, it is your responsibility to bring each item in this warning to the attention of the users of this system.
  • Page 11 Secutron shall not be liable for any delays, breakdowns, interruptions, loss, destruction, alteration or other problems in the use of a product arising our of, or caused by, the software.
  • Page 12: Limited Warranty

    During the warranty period, Secutron Inc. shall, at its option, repair or replace any defective product upon return of the product to its factory, at no charge for labor and materials. Any replacement and/or repaired parts are warranted for the remainder of the original warranty or ninety (90) days, whichever is longer.
  • Page 13: Out Of Warranty Repairs

    MR-23006-AT Remote Multiplex Annunciator Panel Wiring and Installation Manual Out of Warranty Repairs Secutron Inc. will at its option repair or replace out-of-warranty products which are returned to its factory according to the following conditions. Anyone returning goods to Secutron Inc. must first obtain an authorization number.
  • Page 16 No part of this publication may be reproduced, transmitted, transcribed, stored in a retrieval system, or translated into any language or computer language, in any form by any means electronic, magnetic, optical, chemical, manual, or otherwise without the prior consent of Secutron. Canada U.S.A 25 Interchange Way...