Figure 15: Connecting the Alarm and Trouble Relays

Figure 16: Connecting Optional Devices

See installation sheets for the remote devices for
detailed wiring and address setup.
1. Maximum of 4 MR-2605-T per panel.
2. Maximum of 4 MR-2605-AT per panel.
Secur-bus Wiring Chart
Current
(mA)*
15
2,524
30
1,262
45
842
60
631
75
505
90
421
105
361
120
315
135
281
150
252
165
229
180
210
195
194
210
180
225
168
*See module current ratings chart for current drawn by each module attached to the secur-
bus.
14
22-awg Wire
18-awg Wire
ft
ft
ft
769
6,410
384
3,200
256
2,135
192
1,600
154
1,280
128
1,065
110
915
96
800
86
710
77
640
70
580
64
530
59
490
55
455
51
425
16-awg Wire
m
ft
m
1,954
10,160
3,098
976
5,080
1,549
651
3,385
1,032
488
2,540
774
390
2,030
619
325
1,690
515
279
1,450
442
244
1,270
387
216
1,125
343
195
1,015
309
177
920
280
162
845
258
149
780
238
139
725
221
130
675
206
14-awg Wire
ft
m
16,000
4,878
8,000
2,439
5,340
1,628
4,000
1,220
3,200
976
2,670
814
2,285
697
2,000
610
1,780
543
1,600
488
1,455
444
1,335
407
1,230
375
1,145
349
1,065
325