MR-2602 Installation & Operator's Manual
Figure 10: Connecting 4-Wire Smoke Detectors
1. Program as zone type 01, instant alarm.
2. Maximum total loop wire resistance is 100 ohms.
Zone Wiring Chart:
Wire
(Gauge)
18
16
14
4.2 Connecting NAC Devices (Class 'A' and Class 'B')
Figure 11: Connecting NAC Devices (Class 'B')
Figure 12: Connecting NAC Devices (Class 'A')
12
Distance
Distance
(feet)
(meters)
7,690
2,345
12,195
3,717
19,230
5,861
Maximum loop resistance is
100 ohms. Maximum current
in alarm is 60 mA.