Connecting Nac Devices (Class 'A' And Class 'B'); Figure 10: Connecting 4-Wire Smoke Detectors; Figure 11: Connecting Nac Devices (Class 'B'); Figure 12: Connecting Nac Devices (Class 'A') - Secutron MR-2602 Installation Manual

Table of Contents

Advertisement

MR-2602 Installation & Operator's Manual

Figure 10: Connecting 4-Wire Smoke Detectors

1. Program as zone type 01, instant alarm.
2. Maximum total loop wire resistance is 100 ohms.
Zone Wiring Chart:
Wire
(Gauge)
18
16
14

4.2 Connecting NAC Devices (Class 'A' and Class 'B')

Figure 11: Connecting NAC Devices (Class 'B')

Figure 12: Connecting NAC Devices (Class 'A')

12
Distance
Distance
(feet)
(meters)
7,690
2,345
12,195
3,717
19,230
5,861
Maximum loop resistance is
100 ohms. Maximum current
in alarm is 60 mA.

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents