Specifications & Features
Enclosure
A standard 4-gang Electrical Box is used.
Electrical Specifications
•
•
•
•
•
•
Current Drain for Battery Calculations
The maximum normal current drain will be during Lamp Test when all lamps are illuminated on one chassis at a
time. Thus the currents are as follows:
Normal Standby Current = 35 mA
The Normal Standby Current is used for Battery Size Calculations (see the Fire Alarm Control Panel manual) and
includes the current drain for the Trouble Buzzer, Trouble LED, and one Alarm LED. The Maximum Current is
used to calculate the wire size (see the Wiring Instruction).
MR-23006-AT Remote Multiplex Annunciator Panel Wiring and Installation Manual
24 VDC nominal voltage
Slide-Switch Controls, LED indicators, and Keyswitch to enable Controls.
Local Buzzer, Indicators (AC-On, Common Trouble, Signal Silence), and Controls
(System Reset, Lamp Test, Buzzer Silence, Signal Silence).
Annunciation of up to 8 Points.
Not Expandable.
Standby: 35 mA Max., All LED's "On": 90 mA Max.
Maximum Current = 140 mA
5