Appendix A: Power Supply And Battery Calculations - Secutron MR-2900 Installation Manual

Fire alarm control unit
Hide thumbs Also See for MR-2900:
Table of Contents

Advertisement

5.0 Appendix A:
The main AC branch circuit connection for Fire Alarm Control Panel must provide a dedicated continuous power without provision of any disconnect
devices. Use #12 AWG wire with 600-volt insulation and proper over-current circuit protection that complies with the local codes. Refer to 3.0 Technical
Specifications on page 23 for specifications.
Model Number
Fire Alarm Control Unit (includes
MR-2900
MR-2931, MR-2905, MR-2902
MR-2900
Unique LED's
MR-2910
Network Communication Module
MR-2938
Conventional Input Circuit Module
MR-2929
Addressable Input Circuit Module
MR-2909
Addressable Input Circuit Module
MR-2928
Conventional Input Circuit Module
MR-2919
Addressable Input Circuit Module
MR-2614
LED Annunciator
MR-2622
Annunciator Strip
MR-2644
LCD Annunciator
MR-2900-CITY
City Card
MR-2900-DACT
Digital Communication Module
MR-2109-3
Digiquad Module
MR-2944
Annunciator
MR-2915
LED Driver Card
MR-2920
Strip Printer
MR-D1010-R1
Fibre Optic Modem
MR-D1010-R2
Fibre Optic Modem
MR-2690
Isolation Module
Two-Wire Smoke Detectors
Four-Wire Smoke Detectors
Signal Load (bells, horns, strobes, and etc.)
Auxiliary Power Supply for Annunciators, etc.
Total currents (Add above currents)
See 6.0 Appendix B: ULC Listed Compatible Smoke Detectors on page 28 and 7.0 Appendix C: UL Listed Compatible Devices on page 31 for other compatible
devices.
Total Current Requirement: ALARM (B)______ Amps. (Value obtained from column B)
Battery Capacity Requirement:
Battery (AH) = ([STANDBY (A) ______ ] x [(24,60 or 90 Hours) ___ ]) +
([ALARM (B) ______ ] x [Alarm in Hr.] _____) = (C) ______AH
Battery Selection: Multiply (C) by 1.20 to derate battery.
26
Power Supply and Battery Calculations
IMPORTANT NOTICE
POWER REQUIREMENTS (ALL CURRENTS ARE IN AMPERES)
Description
Qty
Total
Standby
Standby
X
0.092
=
X
0.005
=
X
0.005
=
X
0.018
=
X
0.050
=
X
0.001
=
X
0.014
=
X
0.005
=
X
0.020
=
X
0.005
=
X
0.030
=
X
0.020
=
X
0.040
=
X
0.008
=
X
0.075
=
X
0.001
=
X
0.125
=
X
0.075
=
X
0.150
=
X
0.010
=
X
š
=
X
š
=
X
š
=
=
STANDBY
(A)
Alarm
0.107
=
n/a
=
0.005
=
0.101
=
0.050
=
0.001
=
0.094
=
0.005
=
0.155
=
0.125
=
0.070
=
0.315
(reverse polarity mode)
0.035
=
(in alarm (+ load - 65mA for
3 circuits)
0.060
=
0.0008
=
0.075
=
0.010
=
0.800
=
when printing
=
=
=
=
=
=
=
(B)
ALARM
Total
Alarm