INSTALLATION
3
Never connect the base of the generating set directly
to bulkheads or tanks.
1.4

VENTILATION

The generating set normally draws air from the engine
room. Engine rooms with natural ventilation must have
vent openings of adequate size and location to enable the
generating set to operate without overheating. To allow an
ample supply of air within the temperature limits of the
generating set an opening of at least 100 cm2 is required.
A "sealed" engine compartment must have a good
extraction ventilator to maintain reasonable engine room
temperatures. High temperature of intake air reduces
engine
performance
and
temperatures. Air temperatures above 40°C reduce the
engine power by 2% for each 5°C of rise. To minimise
these effects the engine room temperature must not be
more
than
15ºC
above
temperature.
Apply a combination of ventilators, blowers and air intake
ducting to meet the temperature limit. The air inlet ducts
EXHAUST (1)
EXHAUST (1)
40 mm
40 mm
EXHAUST (1)
40 mm
Figure 2
4
increases
engine coolant
the
outside
ambient
air
M-SC 6 and 8
WHISPER 6/8
REMOTE CABLE (2)
REMOTE CABLE (2)
12x0,3mm²
12x0,3 mm
AC CABLE (3)
AC CABLE (3)
M-SC 10
REMOTE CABLE (2)
12x0,3mm²
AC CABLE (3)
should run to the bottom of the engine room to clear fumes
from the bilge and to circulate fresh air. Air outlets should
be at the top of the engine room to remove the hottest air.
An engine room blower should be used as an extraction
ventilator to remove air from the engine room.
In cases where it is impossible to meet the above
mentioned temperature limit by using machine room
ventilation, connections are to be made for an air inlet
directly to the enclosure. With these connections the
generating set can be directly connected to an air duct.
Air inlets should be louvered, where appropriate, to protect
the engine room and to protect the generating set from
water spray. As an extra precaution, the fitting of a cowl
ventilator with a cover box located as high as possible, is
recommended.
FUEL IN (4)
FUEL IN (4)
8mm
8 mm
BATTERY + (5)
BATTERY + (5)
16mm²
16 mm
2
FUEL RETURN (6)
FUEL RETURN (6)
8 mm
8mm
BATTERY - (7)
BATTERY – (7)
16 mm
16mm²
FUEL IN (4)
8mm
BATTERY + (5)
25mm²
FUEL RETURN (6)
8mm
AIRVENT IN (8)
19mm
December 2010 / M-SC 6/8/10 - 3000RPM / EN
WATER IN (8)
WATER IN (8)
19mm
19 mm
AIRVENT OUT (9)
AIRVENT OUT (9)
19mm
19 mm
2
AIRVENT IN (10)
AIRVENT IN (10)
19mm
19 mm
2
WATER IN (10)
19mm
AIRVENT OUT (9)
19mm
BATTERY – (7)
25mm²

Advertisement

Table of Contents
loading

This manual is also suitable for:

M-sc10M-sc8

Table of Contents