32 CONNECTING THE FLUE TO THE BOILER

Note.
a. BEFORE fitting the flue turret, fill the condensate trap
within the boiler by pouring a cupful of water into the flue
outlet A.
b. Take care to ensure that the water is only poured into the
flue outlet, and does not spill into the boiler casing.
1. Insert the flue assembly through the prepared hole in
the wall. Push through and pull back to seal against
outside wall face.
2. Locate the flue turret on the top of the boiler, ensuring
that the turret gasket is in place. Also ensure the turret is
located concentric with the flue aperture on the boiler top
panel. Check that the flue seal (A) located in the top of
the flue manifold is secure and giving an effective seal.
3. Locate the flue into the turret.
4. Secure the flue turret on top of the boiler by inserting the
open ends of the turret clamp under the 2 studs and
fixing it in the middle with the single M5 x 10mm pozi-hex
screw provided.
5. Flues over 1 metre long.
Fix the flue support bracket to the wall, using the wall
plug and wood screw. For standard installations use the
short wood screw.
istor system store -
Installation and Servicing
INSTALLATION
29