40 ASSEMBLING THE ROOF FLUE KIT

Determine the correct height that the flue should terminate
above the roof. If after calculating or measuring the overall flue
height from the top of the boiler, it is necessary to cut both
pipes of assembly A, then ensure they are cut equally leaving
the inner flue tube longer than the outer air tube as supplied.
Ensure the cut pipe ends are free from any burrs.
1. Position the roof flashing plate (supplied separately) over the
hole cut in the roof and insert flue terminal from the roof end.
1
Flat roof tile
weather collar
'X'
34
INSTALLATION
Flue Terminal
Pitched roof tile
weather collar
nm8740
4. If the last extension duct requires cutting, measure 'X', the distance
(outer ducts), between the duct and the terminal and add 100 mm to
this dimension. This gives the length of the last extension duct.
Note. Check the position of the inner flue duct relative to the outer duct
4
on the assembled extension duct(s) and ensure the terminal flue duct
is cut longer than the air duct to ensure engagement in the final flue
duct seal.
5. Finally ensure the roof flashing plate is correctly sealed to the roof.
MAX LENGTH:
2. Push fit the vertical connector (supplied separately) into the
boiler flue connection and retain with the turret clamp and
securing screw (supplied with the boiler). ENSURING THE
GASKETS IN THE BOILER FLUE OUTLET ARE CORRECTLY
FITTED.
3. "Push" fit extension duct (if required (supplied separately)) into
vertical connector.
3
2
nm9429
istor system store -
7.5m
BOILER
Extension
Duct
Turret
clamp
Vertical
connector
Aluminium
sleeve
Installation and Servicing