Troubleshooting Requiring Eaton Service - Eaton 9135 User Manual

5000/6000 va two-in-one ups
Hide thumbs Also See for 9135:
Table of Contents

Advertisement

Table 18. Messages for Troubleshooting Not Requiring Eaton Service
Displayed Details
NO BATTERY
I/O BAD CONNECTION
NO POWER MODULE
NO BATTERY MODULE
INV THERM OVERLOAD
INVERT LIMITATION

Troubleshooting Requiring Eaton Service

Figure 38. Troubleshooting LED
NOTE
Press the
button to display the details described in Table 18.
(
Problem
The battery is incorrectly connected.
Utility input is not connected to the correct
terminals.
The power module is not inserted.
The battery tray is incorrectly connected.
UPS
The
shuts down automatically because of a
major overload.
Short circuit conditions on output devices.
NOTE
In case of multiple fault, press the
further details (see Table 19).
Escape
Up
Down
Enter
Eaton 9135 5000/6000 VA UPS User's Guide 164201726—Rev 4 www.eaton.com/powerquality
Correction
Check battery connections.
Check AC wiring.
Check power module connections (see page 43).
Check battery connections (see page 43).
Check the power drawn by the connected devices
and disconnect any non-priority devices.
Check the installation at the
fault equipment).
button and the
button to get access to
(
Troubleshooting
UPS
output (wiring,
47