Non-Combustible Facing

Non-combustible facing on the front of the fireplace must extend a minimum 16-1/2" from the
top of the glass frame (49-1/2" from the base of the fireplace). Above 16-1/2" combustible
facing may be used (see "Mantel Requirements" on the following page for more details).
Non-combustible facing on the front of the fireplace must extend a minimum 2" to each side of
the glass frame. Beyond 2" combustible facing may be used, but may not protrude more than
4" (see "Mantel Requirements" on the following page for more details).
The maximum depth for non-combustible facing is 6" (includes the fiber board).
Non-Combustible Facing
(tile, rock, marble, etc.)
© Travis Industries
Installation
(for qualified installers only)
Combustible Material
(drywall, etc.)
16-1/2"" Min.
Glass Frame
Fireplace
4090102
Fiber Board (required)
100-01212_000
Figure 23