11.3.4 Connect the Cable to the Outdoor Unit
1
Remove the control board cover from the unit by
loosening the screw.
2
Connection cable between indoor unit and outdoor unit
shall be approved polychloroprene sheathed 4 x 1 .5
2
mm
flexible cord, type designation 245 IEC 57 or
heavier cord.
3
Connect the connection cable between indoor unit and
outdoor unit according to the diagram below.
4
Secure the connection cable onto the control board with
the holder.
5
Attach the control board cover back to the original
position with screw.
6
For wire stripping and connection requirement, refer to
instruction 11.2.5 of indoor unit.
Note:
Isolating Devices (Disconnecting means) should have minimum 3.0 mm contact gap.
Earth wire shall be Yellow/Green (Y/G) in colour and longer than other AC wires for safety reason.
11.3.5 Piping Insulation
1
Please carry out insulation at pipe connection portion as mentioned in Indoor/Outdoor Unit Installation
Diagram. Please wrap the insulated piping end to prevent water from going inside the piping.
2
If drain hose or connecting piping is in the room (where dew may form), please increase the insulation by
using POLY-E FOAM with thickness 6 mm or above.
32