13. Protection Control

13.1 Protection Control for All Operations

13.1.1
Restart Control (Time Delay Safety Control)
The Compressor will not turn on within 3 minutes from the moment operation stops, although the unit is turned on
again by pressing OFF/ON button at remote control within this period.
This control is not applicable if the power supply is cut off and on again.
This phenomenon is to balance the pressure inside the refrigerant cycle.
13.1.2
Total Running Current
1
When the outdoor unit total running current (AC) exceeds X value, the frequency instructed for compressor
operation will be decreased.
2
If the running current does not exceed X value for 10 seconds, the frequency instructed will be increased.
3
However, if total outdoor unit running current exceeds Y value, compressor will be stopped immediately for
3 minutes.
Model
Hz
Operation Mode
Cooling / Soft Dry (A)
Cooling / Soft Dry (B)
Cooling / Soft Dry (C)
Heating
4
The first 30 minutes of cooling operation, (A) will be applied.
Maximum Current Limit
VE9NKE
50
X (A)
Y (A)
3.91
16.76
3.91
16.76
3.91
16.76
11.05
16.76
(VE9NKE)
60
X (A)
Y (A)
X (A)
3.90
16.69
7.41
3.90
16.69
6.44
3.90
16.69
5.14
11.09
16.69
13.02
Cooling
Heating
53
VE12NKE
50
60
Y (A)
X (A)
16.76
7.41
16.69
16.76
6.44
16.69
16.76
5.15
16.69
16.76
13.04
16.69
(VE12NKE)
Y (A)