System Example For The Logamax Plus Gb162-45 And Gb162-50/65/80/100; With Mixer - Buderus Logamax plus GB162 Technical Manual

Gas condensing boiler output range from 2.7 kw to 100 kw
Hide thumbs Also See for Logamax plus GB162:
Table of Contents

Advertisement

6.4.6
System example for the Logamax plus GB162-45 and GB162-50/65/80/100 with Logamatic 4121,
maximum standard equipment level with two heating circuits with mixer
FS
2)
SV
3)
BC10
VK
RK
2)
Fig. 79 Circuit diagram for the system example (index of abbreviations
1)
Hydraulic balancing at the thermostatic valves/zone valves
recommended
2)
For the GB162-65/80/100, pump and safety valve are
integrated into the pump connection assembly (
page 53) – Allow for a safety valve on site if the pump
assembly is not used
3)
For the GB162-50, a separate external pump UPM 15-70
with an external safety set can be used
4)
Differential pressure-dependent pump
The circuit diagram is only a schematic
illustration.
Information regarding all system examples
page 52 ff.
Brief description
• Two heating circuits with mixer with separate time
channels are feasible if the DHW temperature sensor
is connected at the terminal strip of the gas
condensing boiler.
• DHW heating via cylinder primary pump.
• Connection of a DHW circulation pump.
• Individual time channel for DHW.
6 720 645 821 (2010/09) – Logamax plus GB162
PZ
KR
FW
3x1,5 2
2x0,6 2
3x1,5 2
EK
2)
MAG
SMF
KR
PS
FV1
KR
4)
PH1
SH1
VH
FK
WH
Special design information
• The DHW temperature sensor and the cylinder primary
pump are connected at the terminals inside the
fig. 46,
appliance and configured via the MEC2 programming
unit.
• For the appliance, enable "Boiler with pump and low
loss header" at the MEC2 programming unit.
• In combination with a low loss header, the integral
pump in the Logamax plus GB162 must be controlled
subject to output (setting 0).
• For the Logamax plus GB162-45, order the integral
pump as an accessory.
• For the Logamax plus GB162-50, order an external
high efficiency pump UPM 15-70 with safety set.
System examples
Logamatic 4121
FA
2x0,6 2
2x0,6 2
3x1,5 2
2x0,6 2
1)
THV
HK1
4x1,5 2
2x0,6 2
3x1,5 2
1)
ZV (THV)
TWH
HK2
FV2
KR
4)
PH2
4x1,5 2
SH2
(HSM...)
(HKV 3/...)
RH
6 720 642 463-63.1il
page 52)
6