Wm10 Low Loss Header Module; Logamatic Easycom Telecontrol Modem - Buderus Logamax plus GB162 Technical Manual

Gas condensing boiler output range from 2.7 kw to 100 kw
Hide thumbs Also See for Logamax plus GB162:
Table of Contents

Advertisement

4
Heating control
4.5.6

WM10 low loss header module

The WM10 low loss header module regulates the
hydraulic separation between the boiler and the
consumer circuits. This hydraulic separation can be
achieved with a low loss header or via a heat exchanger.
In addition, the WM10 low loss header module can
actuate the secondary pump for the heating circuit
without mixer (heating circuit 1) (system
examples
page 70 f.). Furthermore, the WM10 low
loss header module offers the option of heating DHW via
a cylinder primary pump. When actuating a cylinder
primary pump, heating operation with one heating circuit
with mixer is possible parallel to DHW heating (system
example
page 71).
In systems with Logamax plus GB162 gas condensing
boilers, hydraulic separation is generally required if two
heating circuits are to be connected with individual
pumps.
3
2
1
Fig. 32 WM10 low loss header module (base module)
1
Base module
2
Appliance fuse
3
Access to the spare fuse
4
LED operating and fault displays/indications
5
Plug-in strip for control voltage
6
Plugs for additional components in the Logamatic EMS via
EMS-BUS
7
Plug for the RC... programming unit
8
Plug for the flow temperature sensor (here temperature
sensor for low loss header)
9
Plug-in strip for mains voltage
10
Plug for heating circuit pump
11
Slot for the power supply of additional function modules
(mains output)
12
Plug for mains power 230 V AC, 50 Hz
40
4
5
7 6
8
9
10
11
12
7 747 009 801-23.1il
4.5.7

Logamatic Easycom telecontrol modem

In the form of the Logamatic Easycom, Buderus offers an
affordable telecontrol modem for remote monitoring and
setting of parameters in small and medium-sized heating
systems. It is available as the EM modular version
including parameter software and cable.
The following are the essential features of the telecontrol
modem:
• May be connected to any control unit of the Logamatic
4000 or EMS families; BUS-enabled for the
subscribers of a BUS system; with an additional
potential-free message input
• Connection via an analogue telephone connection or,
with an adaptor, via an ISDN system; highdata transfer
speed (56 kBit/s)
• Complete remote scanning and setting of parameters
of the connected system via PC software Logamatic
ECO-SOFT with operating mode changeover via
telephone (holiday home function)
• Remote monitoring of the connected system with
automatic fault message to any three recipients;
possible recipients are fax, mobile phones (SMS via
D1, D2 or E-Plus), PC call centres (with
ECO-MASTERSOFT PC software) or email addresses
• Prepared for firmware updates via software download
1
Fig. 33 Logamatic Easycom telecontrol modem (EM
module version)
1
ON/OFF key
2
Standby display
3
"Message" display
4
"Telephone line busy" display
5
"Service" display
6
"Service" or "Restart" key
7
Terminal cover for EM module version
6 720 645 821 (2010/09) – Logamax plus GB162
2
3
4
5
6
7
6 720 641 280-15.1il