Quadra-Fire TOPAZ-MBK-IPI Installation Manual page 25

Hide thumbs Also See for TOPAZ-MBK-IPI:
Table of Contents

Advertisement

Existing Masonry Chimney
Prior to installing the gas stove, ensure that the existing chimney is functionally sound and clean.
• Have the chimney and adjacent structure inspected and cleaned by qualified professionals. Hearth & Home
Technologies recommends that NFI or CSIA certified professionals, or technicians under the direction of certified
professionals, conduct a minimum of a NFPA 211 Level 2 inspection of the chimney.
• Replace component parts of the chimney and fireplaceas specified by the professionals.
• See Section 11 for venting components.
Type A & B Co-Axial to Co-Linear
Co-Axial to
Co-Linear Connector
(Part 46DVA-GCL)
Type C - Up & Out Installation
TOP ADAPTOR
(Included in Masonry Chimney
Conversion Kit)
RETRO CONNECTOR
(Included in Masonry Chimney
Conversion Kit)
90° ELBOW
DIRECT VENT PIPE
(Length as required)
Figure 4.22
25
Quadra-Fire • TOPAZ-MBK-IPI, TOPAZ-D-PMH-IPI, TOPAZ-D-MBK-IPI, TOPAZ-D-CSB-IPI Installation Manual • 2341-980_R10 • 11/15
See COAXIAL/COLINEAR
Section and Figure 4.31.
Chimney Liner Termination Cap
(Included in Chimney Liner
Termination Kit)
3 in. (76mm) Flex Liner
(Included in Chimney Liner
Termination Kit)
Showing two 30 ft.
(9m) Sections of
Flex Liner
TERMINATION CAP
(Included in Link-Stove kit)
FLASHING
(Included in Masonry
Chimney Conversion Kit)
4 in. (102mm) FLEX LINER
(Included in Link-Stove kit)
Co-Axial to Co-Linear
Connector
(Part 46DVA-GCL)
Type D - Hearth Mount
Alcove Clearance to
Combustibles must be
maintained. See Figure 3.2.
Co-Axial to Co-Linear Connector
(Part 46DVA - GCL)
Chimney Liner Termination Cap
(Included in Chimney Liner Termination Kit)
30 ft. (9m) of 3 in. (76mm) Flex
Liner Exhaust Section
(Included in Chimney Liner Termination Kit)
This section of the chimney
must be sealed
The chimney must be sealed from the
4 ft. (1m) section to termination using
a smoke shelf or a flue restrictor. The
seal should be a minimum of 6 in.
(152mm) below the end of the 4 ft.
(1m) Air Intake section.
4 ft. (1m) of 3 in. (76mm)
Flex Liner Air Intake Section
(Included in Chimney Liner Termination Kit)
Chimney Liner Termination Cap
(Included in Chimney Liner
Termination Kit)
30 ft. (9m) of 3 in. (76mm)
Flex Liner Exhaust Section
(Included in Chimney Liner
Termination Kit)
This section of the
chimney must be sealed
Chimney must be sealed
from 4 ft. (1m) section to
termination using a smoke
shelf or a flue restrictor.
Seal should be a minimum of
6 in. (152mm) below end of
4 ft. (1m) Air Intake section.
4 ft. (1m) of 3 in. (76mm)
Flex Liner Air Intake Section
(Included in Chimney Liner
Termination Kit)