Tab.5
Hydraulic specifications
Water content (excluding expansion vessel)
Minimum operating pressure
Maximum operating pressure
Maximum water temperature
Pressure loss of hydraulic circuit at Δt = 10K
Pressure loss of hydraulic circuit at Δt = 15K
Pressure loss of hydraulic circuit at Δt = 20K
Tab.6
Data on the combustion gases
NOx emission according to EN267
Flue gas mass flow rate Pn 40/30°C
Flue gas circuit volume
Flue gas temperature Pn 80/60°C
Required depressurisation at the nozzle
Number of cast iron parts
Number of baffle plates
Tab.7
Electrical characteristics
Power supply voltage
Electrical protection rating
Maximum absorbed power - Elmax
Minimum absorbed power - Elmin
Absorbed power - Stand-by - Psb
Tab.8
Other characteristics
Maximum operating temperature
Settings range for the heating water temperature
Settings range for the domestic hot water temperature
Safety thermostat
Weight empty
Tab.9
Burner specifications
Burner type
Fuel flow rate
7615193 - v01 - 09072015
3 Technical specifications
Unit
EFU 22
litre
24.5
MPa (bar)
0.05 (0.5)
MPa (bar)
0.3 (3)
°C
90
mbar
19
mbar
9
mbar
5
Unit
EFU 22
mg/kWh
Class 3
kg/h
36
litre
41
°C
<160
Pa
5
Part
4
Part
2
Unit
EFU 22
VAC
230
IP
21
W
143
W
50
W
4
Unit
EFU 22
°C
90
°C
30 - 90
°C
40 - 65
°C
110
kg
166
Unit
EFU 22
RDB 2.2
kg/h
2.02
EFU 29
30
0.05 (0.5)
0.3 (3)
90
34
15
9
EFU 29
Class 3
48
51
<160
5
5
2
EFU 29
230
21
144
50
4
EFU 29
90
30 - 90
40 - 65
110
191
EFU 29
RDB 2.2
2.69
EFU
11

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Neovo econox efu 29