Montigo H38DF PRC Installation & Maintenance Manual page 15

Panorama indoor residential gas fireplace
Table of Contents

Advertisement

Notes Wall Mounted Terminations: REAR VENT
All dimension lengths for vertical or horizontal runs are
measured from center of the vent pipe.
Venting runs must fall within the limits set by the venting
graphs, see Figure 14 or 14a.
Fireplace must be converted to Rear Vent configuration
prior to running vent, see Figure 8 and 8a.
The Venting Graph
Measure the vertical height from the fireplace hearth to the centre
of the termination and the horizontal run from the fireplace flue
collar to the wall flange of the termination. Plot on the Venting
Graph Figure 14 or 14a with an 'X'.
If the 'X' falls on or above the top boundary of the shaded area, the
installation is acceptable.
Example A: (Acceptable Installation)
If the vertical dimension from the hearth is 114" and the
horizontal run to the wall flange of the vent termination is
126", this would be an acceptable installation.
Example B: (Unacceptable Installation)
If the vertical dimension from the hearth is 66" and the horizontal
run to the wall flange of the vent termination is 84", this would
NOT be an acceptable installation.
Example C: (Unacceptable Installation)
If the vertical dimension from the floor of the fireplace is 72"
and the horizontal run to the wall flange of the vent termination
is 144", this would NOT be an acceptable installation.
Acceptable vent run
within non-shaded area.
B
46"
33"
12"
Figure 14. H38PR* or HL38PR* Rear Vent Venting Graph for wall mounted
terminations.
XG0211 - 151126
Installation
A
C
59"
Unacceptable vent run
within shaded area.
If your installation does not fall with-
in the venting graph parameters,
please contact a local Montigo
dealer for Power Venting options.
H*38DF PRC Panorama Indoor Gas Fireplace
Acceptable vent run
within non-shaded area.
B
59"
42 "
Figure 14a. HP38PR*Rear Vent Venting Graph for wall mounted terminations.
Hearth
Figure 15. H38PR* or HL38PR* Straight run, Rear Vented, wall mounted
termination. The vent run must comply with the Venting Graph for Rear
vent, wall mounted terminations Figure 14. Note: HP38PR* CANNOT be
straight run, rear vented with a wall mounted termination.
Section:
A
C
Unacceptable vent run
within shaded area.
If your installation does not fall with-
in the venting graph parameters,
please contact a local Montigo
dealer for Power Venting options.
NOTE:
12" MAX. horizontal
run with no vertical lift.
PXT Extension
RHS101 Heat
Shield
Termination
12" MAX.
33 1/2"
Exterior
Wall
.
Page 15