Safety Valve; Connection Of The Water Circuit For Domestic Use - DeDietrich GT 330 Installation And Service Manual

Fuel oil/gas-fired boiler
Hide thumbs Also See for GT 330:
Table of Contents

Advertisement

4. Installation
4.5.4

Safety valve

The safety valve must be connected to the boiler outlet and no other
valve or flap must be interposed between it and the boiler.
Minimum safety valve flowrate as a function of maximum boiler nominal output
Minimum relieving capacity
Maximum gross boiler output
Unit
(a) = kW
(b) = lb/h
(c) = MBtu/h
(d) = Kg/h
4.5.5

Connection of the water circuit for domestic use

See: Domestic hot water calorifier instructions.
22
Example
Maximum boiler nominal output is 200 kW.
Minimum safety valve flowrate must be 700 Kg/h.
GT 330
05/03/2013 - 300007650-001-02