DELTA DORE DELTA 200 Installation Manual page 9

Outdoor-temperature-driven controller for hot water heating
Hide thumbs Also See for DELTA 200:
Table of Contents

Advertisement

Activation
Menu C9: Valve operating time
Corresponds to the maximum time for the valve to open or close.
Setting the valve operating time (zone 1)
Default setting: C09=0 and the time set is 120 seconds.
IMPORTANT: To determine the valve operating time, refer to the valve
documentation.
Menu C10: Anticipation value of zone 1
Anticipation is the time it takes to reach the desired temperature at the time
specified in the program, namely:
T
= (Zone 1 setting - Zone 1 T° as measured) x Setting C10.
anticipation
It keeps the temperature from rising too quickly, which would consume too
much energy.
Example: You are in economy mode and the room temperature is 17°C.
The Comfort temperature setting is 20°C.
C10 is set to 30 min/°C.
For room temperature to have reached 20°C by the time Comfort mode is
programmed to come on, heating will need to begin 1.5 hours in advance:
Ta = (20°C - 17°C) x 30 min./°C = 1:30.
Changes not allowed
Setting the anticipation time
Changes allowed (from 0 to 120 minutes/°C in increments of 5)
for zone 1
Upon activation, the time is set to 30 min./°C.
Default setting: C10=0 and anticipation time is set to 30 minutes/°C.
Changes not allowed
Changes allowed (from 1 to 240 seconds)
Upon activation, the time is set to 120 seconds.
OK
OK
- 16 -
Tip: Initially, use the default setting (30 min/°C).
- If the desired temperature is reached too quickly, set a higher value
(e.g. 45 min./°C).
- If the desired temperature is not reached quickly enough, set a lower
value (e.g. 20 min./°C).
IMPORTANT : If you do not require anticipation, set C10 to 0.
Menu C11: Setting the temperature increase time for
zone 2
This is the period during which overpower is used in zone 2 to increase the
temperature.
The following formula is used when switching from Economy to Comfort
mode: T
= setting C11 x (zone 2 setting - outdoor T°)
overpower
The following formula is used when switching from Shutdown or Frost
Protection to Economy or Comfort mode:
T
= 2 x setting C11 x (zone 2 setting - outdoor T°)
soverpower
Setting the overpower time for zone 2
Upon activation, the time is set to 5 min./°C.
Menu C12: Control differential for zone 2
Setting the control differential for zone 2
Default setting: C12=0 and the differential is set to 3°C.
Changes not allowed
Changes allowed (from 0 to 20 minutes/°C)
Upon activation, the time is set to 5 min./°C.
OK
Changes not allowed
Changes allowed (from 0.5°C to 10°C)
Upon activation, the temperature is set to 3°C.
OK