4.5.3
Hydraulic connection of the heating circuit
Water flow in the boiler
The water flow in the boiler when the burner is operating must
correspond with the following formulae:
- Nominal water flow Qn = 0.86 Pn/20.
- Minimum flow Qmin = 0.86 Pn/45 (this flow also corresponds with
the minimum recycle flow in the boiler).
- Maximum water flow Qmax = 0.86 Pn/5.
3
Qn = flow in m
/h.
Pn = Nominal output (full boiler output) in kW.
Operation in cascade
After stopping the burner:
- Timeout required before the order to close a 2 way valve: 3 min.
- Switch a possible shunt pump (located between the boiler and a
butterfly valve) off via the end of run contact of the butterfly valve.
Operation with 2-stage burner
- The water temperature in the boiler is maintained at 50°C or more;
The first stage must be set to a minimum of 30% of the nominal
stage.
- Operation at modulated low temperature (minimum outlet
temperature: 40°C); The first stage must be set to a minimum of
50% of the nominal stage.
Operation with modulating burner
- The water temperature in the boiler is maintained at 50°C or more:
The burner can modulate down to 30% of the nominal stage.
- Operation at modulated low temperature (minimum outlet
temperature: 40°C); The burner can modulate down to 50% of the
nominal stage.
05/03/2013 - 300011893-001-02
GT 430